Setup Menu

A.6.3 Setup Sensor

For details on this feature, see 7.5 - Setup System - Setup Sensor.

Setup Sensor

SETUP SENSOR

Setup for analog

input points

Select sensor to edit

SENSOR

VALUE

1=SENSOR_1

80.0

DEG

2=SENSOR_2 ------

DEG

3=SENSOR_3

80.0

DEG

4=SENSOR_4

79.5

RH

5=RETURN TO SETUP MENU 6=RETURN TO MAIN MENU

SELECT A NUMBER:1

>IS THE SENSOR CONNECTED-YES(Y) OR NO(N)? >[N]

>[]

>CHANGE SENSOR LABEL(8 CHARACTERS MAX). >[SENSOR_1]

>[]

>CHANGE UNITS LABEL(3 CHARACTERS MAX). >[DEG]

>[]

>CHANGE 4 mA VALUE(+045.0 TO +096.0). >[+045.0] >[]

>CHANGE 20 mA VALUE(+045.0 TO +096.0). >[+096.0] >[]

>CHANGE OFFSET VALUE(-999.9 TO +999.9). >[+000.0] >[]

>IS SENSOR AN ALARM(AL) OR EVENT(EV)? >[AL]

>[]

>IS SENSOR ALARM LATCHED-YES(Y) OR NO(N)? >[Y]

>[]

>CHANGE LOW SETPOINT. >[-0015.0] >[]

>CHANGE HIGH SETPOINT. >[+0015.0] >[]

>DELAY TIME BEFORE TRIGGER (MM:SS)? >[00:01] >[]