Emerson user manual AC8 Specifications

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 86
Image 86

Specifications

8.0SPECIFICATIONS

8.1AC8 Specifications

 

Transformer Module

 

 

 

 

 

115VAC

 

230VAC

Power

UML11500

 

UML23000

Requirements

115VAC ±10%

 

230VAC ±10%

 

of nominal;

 

of nominal;

 

60Hz, 4A,

 

50Hz, 0.5A,

 

460VA

 

115VA

Dimensions

 

18 x 2-3/4 x 18

W x D x H, in. (mm)

(457.2 x 69.85 x 457.2)

Weight (Assembled)

20.56 lb. (9.33 kg)

Enclosure Type

 

NEMA 1

Liquid Crystal Display (LCD)

Four line, 20 character, backlit

Mounting Surface

Building Wall or Structural Member

Ambient Operating

32ºF to 104ºF (0ºC to 40ºC)

Environment

0% RH to 95% RH (non-condensing)

Processor Specifics

 

 

 

Model

Motorola XC68HC812A4

 

 

 

Clock speed

 

16MHz

Total RAM

 

256Kb

 

 

 

Total FLASH

 

4M

 

 

 

Total EEPROM

 

4K

A/D Resolution (Analog IN)

 

12 Bit

 

 

 

Modem Type Embedded

 

14.4K bps

 

 

Clock Type

Real-Time Clock

Clock battery backup type

Lithium Cell (non-replaceable)

 

 

Clock battery life

7 years, constant, no power

 

 

Modem battery backup type

Nickel Cadmium (replaceable)

Modem battery life

10 minutes at full load

 

 

 

 

Communications

 

 

 

Local Communications

 

RS232

Remote Communications

 

 

 

Modem (9600-N-8-1)

Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1

Supported pagers

9600 E-7-1 supports TAPI protocol version 1.8

SiteScan Web

IGM Protocol, EIA422

 

 

 

Transformer Module

Agency Listings

 

 

 

115VAC

 

230VAC

 

(TM115)

 

(TM230)

UL

UL1012

 

UL1585

 

 

 

CSA

C22.2 No. 66 and

C22.2 No. 107.1

 

CE

 

Yes

 

 

 

FCC Compliance

 

N/A

 

 

 

 

Inputs & Outputs (Quantity)

 

 

 

Digital Inputs (8)

Dry Contact Closure 24VDC, 10 mA

 

 

Analog Inputs (4)

4-20 mA signal input with selectable

power source of 12VDC or 24VDC

 

Digital Outputs (8)

 

24VAC, 3A

 

 

 

Common Alarm Outputs (2)

 

24VAC, 3A

 

 

 

 

NOTE

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.