Emerson AC8 user manual A.6.1 Setup Inputs, A.6.2 Setup Common Alarm, Setup Menu

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 105
Image 105
A.6.1 Setup Inputs

Setup Menu

A.6.1 Setup Inputs

For details on this feature, see 7.3 - Setup System - Setup Inputs.

Setup Inputs

SETUP INPUTS

 

Setup input

of device

 

Select input to edit

 

INPUT

DEFINITION

****************************

 

 

NO=NORMALLY OPENED

1=DEVICE_1

NO-EV-NL-00:01

NC=NORMALLY CLOSED

2=DEVICE_2

NO-AL-L -00:01

 

3=DEVICE_3

NC-EV-NL-00:01

EV=EVENT

4=DEVICE_4

NO-AL-L -00:01

AL=ALARMABLE

5=DEVICE_5

NC-AL-L -00:01

 

6=DEVICE_6

NO-EV-NL-00:01

NL=NOT LATCHED

7=DEVICE_7

NO-AL-L -00:01

L =LATCHED

8=DEVICE_8

NC-EV-NL-00:01

 

9=RETURN TO

SETUP MENU

MIN:SEC=DELAY TIME BEFORE

0=RETURN TO

MAIN MENU

INPUT WILL TRIGGER

NOTE:EVENT CANNOT BE LATCHED

****************************

SELECT A NUMBER:1

>CHANGE LABEL(8 CHARACTERS MAX). >[DEVICE_1]

>[]

>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)? >[NO]

>[]

>IS INPUT AN ALARM(AL) OR EVENT(EV)? >[EV]

>[]

>IS ALARM LATCHED-YES(Y) OR NO(N)? >[N]

>[]

>DELAY TIME BEFORE TRIGGER (MM:SS)? >[00:01] >[]

A.6.2 Setup Common Alarm

For details on this feature, see 7.4 - Setup System - Setup Common Alarm.

Setup Common Alarm

SETUP COMMON ALARM

 

Select if the common

 

alarm relay contact

 

is to reset with

 

silence alarm

CURRENT

 

SETTING

1=SETUP COMMON ALARM

N

2=RETURN TO SETUP MENU

 

3=RETURN TO MAIN MENU

 

SELECT A NUMBER:1

 

 

 

>RESET COMMON ALARM WITH SILENCE-YES(Y) OR NO(N)? >[N]

>[