Emerson AC8 Log In and Choose Override Output, Select an Output, Main Menu, Login, Select Output

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 83
Image 83
Log In and Choose Override Output

System and Control Options

7.12Override Output

The Override Output feature allows you to manually change the state of any digital output to ON or OFF, overriding automatic control by the AC8 (the default setting for all outputs). This menu also allows you to release the manual override, returning any output to automatic control.

There are two ways to override automatic control of outputs:

Use the Override Output menu, as described in this section, to turn any output ON or OFF.

Use the hardware switch on the AC8 circuit board to force all eight outputs ON at the same time (see Item I - Manual Override Switch (outputs) in 1.7 - Controller Board Overview).

After an output is forced manually ON or OFF through the Override Output menu, it remains in that state until returned to automatic control through this menu.

Table 32 summarizes the four types of control, including the abbreviated message that appears on the LCD and in log reports.

Table 32 Automatic / manual control - output points

Message

 

Description

 

 

 

AUTO

Automatic

Controlled by AC8

(default for all outputs)

 

 

FORCE ON

Manually ON

This output has been forced ON

 

 

(operating) or OFF via the Override

FORCE OFF

Manually OFF

Output menu

 

 

 

 

 

All outputs have been forced ON

 

Manually ON

(operating) via the hardware switch on

HW FORCE ON

the circuit board (see Item I - Manual

(all outputs)

 

Override Switch (outputs) in 1.7 -

 

 

 

 

Controller Board Overview)

 

 

 

To force an output point ON or OFF or return it to automatic control:

Log In and Choose Override Output

• From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter ↵ (see 7.1 - Login for help).

• Enter your password at the Login screen.

• From the System and Control Menu, use the arrows ↑↓ to choose Override Output, then press Enter ↵ .

Select an Output

The Select Output menu, shown at right, displays the current status of all eight outputs.

Use the arrows ↑↓ to choose the output you want—for example, Device_1—and press Enter ↵ .

Turn Output ON or OFF / Return to Automatic

• From the Override Output menu, use the arrows ↑↓ to choose one of these options:

AUTO - return to automatic control

FORCE ON - manually turn this output ON (operating)

FORCE OFF - manually turn this output OFF

Press Enter ↵ .

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑↓ =NEXT

=SELECT

Login

LOGIN

AAAA

↑↓ =SELECT =NEXT/END

System & Control Menu

SETUP SYSTEM

>OVERRIDE OUTPUT

CLEAR ALARMS & LOGS ↑↓ =NEXT =SELECT

Select Output

OVERRIDE OUTPUT

> DEVICE_1

AUTO

 

DEVICE_2

AUTO

 

↑↓ =NEXT

=SELECT

 

DEVICE_3

AUTO

 

DEVICE_4

FORCE ON

Override Output

SELECT DEVICE_1

FORCE ON ↑↓ =SELECT =END

75

Page 83
Image 83
Emerson AC8 Log In and Choose Override Output, Select an Output, Turn Output ON or OFF / Return to Automatic, Main Menu