Emerson AC8 7.9.3Setup Site ID, 7.9.4Connect Battery, Setup System Info Menu, Battery alarms

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 67
Image 67
7.9.3Setup Site ID

System and Control Options

7.9.3Setup Site ID

You may enter a Site ID to identify the AC8’s location, using a name that may consist of up to 40 characters (see Table 14 for valid charac- ters). The Site ID will appear with each alarm.

To enter or change the Site ID:

• From the Setup System Info Menu, use the arrows ↑↓ to choose Setup Site ID, then press Enter ↵ .

To enter a Site ID:

Use the arrows ↑↓ to choose a character.

Press Enter ↵ to advance to the next character position.

If the Site ID is less than 40 characters, you may enter an underscore (_) character to indicate the end of the name.

When finished, press Enter ↵ again.

Setup System Info Menu

SETUP SYSTEM INFO CHANGE PASSWORD CHANGE DATE & TIME ↑↓ =NEXT =SELECT

>SETUP SITE ID CONNECT BATTERY SETUP SERV PH NUM FACTORY DEFAULTS

Setup Site ID

SETUP SITE ID

AAAAAAAAAAAAAAAAAAAA

AAAAAAAAAAAAAAAAAAAA ↑↓ =SELECT =NEXT/END

7.9.4Connect Battery

By default, the AC8 checks the battery and sounds an alarm when the power fails, the battery runs low or the battery needs to be checked. The battery’s main purpose is to provide enough power to the modem to notify pagers of a power loss.

NOTE

The battery will continue to power and provide full operation of the AC8 with the exception of powering the analog inputs (sensors). The battery will provide backup for a minimum of 10 minutes.

Using the following procedure to disconnect the battery will disable battery alarm features only. The battery itself will continue to provide backup. If battery backup is not desired, the battery must be unplugged from the circuit board. This can be done by removing the battery leads from the jumpers (see 2.4.2 - Connecting the Battery Pack).

The default is to connect the battery. However, there may be times that you want to disconnect the battery so that it does not provide backup.

Table 25 shows battery problems that will affect operation.

Table 25 Battery alarms

Result of Battery

Action

Message Generated

Battery falls below a minimum charge.

Battery will not provide battery backup.

LOW BATTERY

 

 

 

Battery is connected to the circuit board but

Battery will not provide battery backup.

CHECK BATTERY

not recognized by the circuit board.

 

 

Battery is unplugged from the circuit board.

Battery will not provide battery backup

BATTERY UNPLUGGED

Utility power (24VAC) to the circuit board is

AC8 board will not be able to function

LOSS OF POWER

too low to power the board.

properly.

 

To connect or disconnect the battery:

• From the Setup System Info Menu, use the arrows ↑↓ to choose Connect Battery, then press Enter ↵ .

Use the arrows ↑↓ to choose Y (Yes - the battery is connected) or N (No - the battery is not connected), then press Enter ↵ .

Setup System Info Menu

SETUP SYSTEM INFO CHANGE PASSWORD CHANGE DATE & TIME ↑↓ =NEXT =SELECT

SETUP SITE ID

>CONNECT BATTERY SETUP SERV PH NUM FACTORY DEFAULTS

Connect Battery

IS THE BATTERY

CONNECTED? Y

↑↓ =Y/N

=END

59

Page 67
Image 67
Emerson AC8 user manual 7.9.3Setup Site ID, 7.9.4Connect Battery, Setup System Info Menu, Battery alarms