Emerson AC8 Log In and Choose Setup System, Select a Sensor to Configure, Setup System Menu

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 48
Image 48
Select a Sensor to Configure

System and Control Options

7.5Setup System - Setup Sensor

The AC8 has four analog sensor input points that may be configured individually. The panel monitors connected equipment for any 4-20 mA input—for example, temperature and humidity. Each sensor input is dedicated to a specific zone:

Sensor_1 is for Zone 1

Sensor_2 is for Zone 2

Sensor_3 is for Zone 3

Sensor_4 is for Zone 4

To configure a sensor:

Log In and Choose Setup System

• From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter ↵ (see 7.1 - Login for help).

• Enter your password at the Login screen.

• From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter ↵ .

Select a Sensor to Configure

• From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Sensor and press Enter ↵ .

From the Select Sensor Menu, choose the sensor you want—for example, Sensor_1—and press Enter ↵ .

Table 17 shows sensor features that may be changed, along with the default settings. By default, sensor inputs are not connected.

To activate a sensor input, you must specify it as connected and enter corresponding values for 4 and 20 mA, as well as high and low set- points. Other features that may be altered include the name of the sen- sor, the abbreviation for the units, and defining the sensor as alarmable or as an event.

• Alarmable sensors may be Latched (Y) or Unlatched (N).

Setup System Menu

SETUP INPUTS SETUP COMMON ALARM

>SETUP SENSOR

↑↓ =NEXT =SELECT

SETUP ZONES SETUP OUTPUTS SETUP MODEM&PAGERS SETUP SYSTEM INFO SETUP OPERATION SETUP I/O MATRIX

Select Sensor Menu

SELECT SENSOR

>SENSOR_1 +80.00 DEG

SENSOR_2 ------ DEG ↑↓ =NEXT =SELECT

SENSOR_3

SENSOR_4 +79.50 RH

Event status allows you to monitor a sensor’s high and low setpoints—and use those setpoints to change the status of an output, if desired—without triggering an alarm. Events are always Unlatched.

You may also specify a time delay before the AC8 responds to an alarm or event.

Use the steps following Table 17 to change the default settings for any analog sensor input.

Table 17 Default settings - analog sensor inputs

Feature

Default

Other Options

 

 

 

CONNECTED*

N (Not connected)*

Y (Connected)**

LABEL

SENSOR_1

Any name (up to eight characters)

UNITS

DEG

Any units (up to three characters)

4 mA

+045.0

Can define up to two decimal places—for example, -99.99

20 mA

+096.0

Can define up to two decimal places—for example, +99.99

OFFSET

+000.0

Can define up to two decimal places—for example, +00.00

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

N (Unlatched)

Y (Latched)

LOW SETPT

+0050.0

Can define up to two decimal places—for example, -999.99

HIGH SETPT

+0090.0

Can define up to two decimal places—for example, +999.99

SENSOR DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

*If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces). ** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.

If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.

40

Page 48
Image 48
Emerson AC8 user manual Log In and Choose Setup System, Select a Sensor to Configure, Setup System Menu, Select Sensor Menu