System and Control Options

7.9.6Setup Serv Ph Num - Enter Phone Number

The Service Phone Number (Serv Ph Num) is used for remote monitoring by Liebert Global Services. The number is designed to allow remote monitoring services to connect to the AC8. All alarms will be sent to this number. When an alarm occurs, this number is dialed before any of the four pager numbers.

To use the service phone number features, be sure to connect the phone line connector to a telephone wall jack using an RJ11 cord, as described in 3.6.2 - Phone Line Connector.

Table 26 Service phone number dialing results

Result of Dialing

Action

Message Generated

 

 

 

Successful

 

 

 

Unsuccessful due to:

 

 

 

 

 

Busy signal / no answer /

AC8 generates message after all three

Unsuccessful Page

no dial tone

redial attempts have failed, dials next configured pager.

(Event Log)

General modem

AC8 resets modem, generates

Modem Reset

communication problem

message, redials up to three more times.

(Event Log)

No communication with modem

AC8 generates messages, makes no

Modem Internal Fault

(Active Alarm Report,

(internal hardware problem)

further dialing attempts.

Alarm History Log)

 

 

 

 

 

To set up the service phone number:

• From the Setup System Info Menu, use the arrows ↑↓ to choose Setup Serv Ph Num, then press Enter .

See Table 27 for guidelines on entering the phone number, which may consist of up to 40 characters. To enter the phone number:

Use the arrows ↑↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

Table 27 Guidelines for dialing service phone number

Device type

Required entries

Example

 

 

 

Remote

The first character must be “M”.

M18005551212

modem

 

 

Device type

Optional entries

Example

 

 

 

 

Use “9” if needed to access an outside

M918005551212

 

line—place after first character (M).

 

 

Use “W” to wait for a second dial tone

M9W18005551212

All types

before dialing if the phone system has

 

of devices

two dial tones (initial tone and a second

 

 

tone for outside line)—place after “9”

 

 

(before the number to be dialed).

 

 

Use “,” (comma) to pause two seconds.

M1,8005551212

 

 

 

Setup System Info Menu

SETUP SYSTEM INFO CHANGE PASSWORD CHANGE DATE & TIME ↑↓ =NEXT =SELECT

SETUP SITE ID

CONNECT BATTERY

>SETUP SERV PH NUM FACTORY DEFAULTS

Setup Serv Ph Num

ENTER PHONE NUMBER

M18005551212

↑↓ =SELECT =NEXT/END

63

Page 71
Image 71
Emerson AC8 Setup Serv Ph Num Enter Phone Number, Service phone number dialing results, Setup Serv PH NUM Factory Defaults