Setup Menu
Table 36 AC8 - other default settings
DEFAULT SETTINGS - operation features (FROM Table 28)
Feature | Default | Other Options |
|
|
|
AUTO SEQUENCING | OFF (Deactivated) | ON (Activated), 12h (Activated for |
|
|
|
STANDBY TESTING | OFF (Deactivated) | ON (Activated) |
|
|
|
FAILED STANDBY | N (Deactivated) | Y (Activated) |
|
|
|
HOLD DELAY | 10:00 (No delay) | Any time (in minutes and seconds) from 00:00 to 99:59 |
|
|
|
RESTART | 00:06 (No delay) | Any time (in minutes and seconds) from 00:00 to 99:59 |
|
|
|
STAGING | OFF (Deactivated) | ON (Activated) |
|
|
|
JUMPER SETTINGS |
|
|
|
|
|
Feature | Default | Other Options |
|
|
|
Digital output | OFF - Normally Open | ON - Normally Closed |
|
|
|
NOTE: The jumper position has no effect on the contact when the AC8 has power.
12VDC/24VDC analog input jumper | 24VDC | Acceptable voltage for all four | |
|
|
| |
422 TERM jumper | Default: jumpered | ||
(connected) | |||
|
| ||
485 TERM jumper | Default: jumpered | ||
(connected) | |||
|
| ||
EPOP jumper | Disabled | Enable to use the EPOP input | |
|
|
| |
Audible horn | Enabled | May be disabled via the audible horn jumper | |
|
|
| |
Manual Override switch | Off (outputs controlled by | On (Turn on all output relays) | |
| programming) |
| |
DEFAULT SETTINGS - MODEM (FROM Table 21) |
| ||
|
|
| |
Feature | Default | Other Options | |
|
|
| |
|
| Any string (up to 40 characters); for international | |
Initialization String (InitString) | ATS0=1 | dialing, add +GCI=xx, where xx is the country code | |
|
| (except B5 | |
Enable Modem Diagnostic Messages | N (disable) | Y (enable) | |
|
|
| |
Modem Dial Prefix | ATE0X4DT | Any string | |
|
|
| |
Modem Hang Up Delay After a Call | 10 seconds | Any number (up to 99 seconds) | |
|
|
| |
DIP SWITCH SETTINGS |
|
| |
|
|
| |
Feature | Default | Other Options | |
|
|
| |
All are OFF (down) | May be used to reset password to factory default (see | ||
9.9.1- Change Password) | |||
|
| ||
OTHER SETTINGS |
|
| |
|
|
| |
Feature | Default | Other Options | |
|
|
| |
Change state of outputs - automatic | AUTO (automatic control) | Force an output ON / OFF via Manual Output Ctrl menu | |
or manual control |
| Force all outputs ON via hardware switch | |
Password | AAAA | Any 4 characters (see Table 14 for valid characters) | |
|
|
| |
Reset common alarm with silence | N (not reset) | Y (reset with silence) | |
|
|
| |
Battery connected | Y (connected) | N (not connected) | |
|
|
|
118