Table 36 AC8 - other default settings

Setup Menu

Table 36 AC8 - other default settings

DEFAULT SETTINGS - operation features (FROM Table 28)

Feature

Default

Other Options

 

 

 

AUTO SEQUENCING

OFF (Deactivated)

ON (Activated), 12h (Activated for 12-hour intervals)

 

 

 

STANDBY TESTING

OFF (Deactivated)

ON (Activated)

 

 

 

FAILED STANDBY

N (Deactivated)

Y (Activated)

 

 

 

HOLD DELAY

10:00 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

 

 

 

RESTART

00:06 (No delay)

Any time (in minutes and seconds) from 00:00 to 99:59

 

 

 

STAGING

OFF (Deactivated)

ON (Activated)

 

 

 

JUMPER SETTINGS

 

 

 

 

 

Feature

Default

Other Options

 

 

 

Digital output loss-of-power jumpers

OFF - Normally Open

ON - Normally Closed

 

 

 

NOTE: The jumper position has no effect on the contact when the AC8 has power.

12VDC/24VDC analog input jumper

24VDC

Acceptable voltage for all four two-wire analog sensors

 

 

 

422 TERM jumper

Default: jumpered

None—do NOT change factory default

(connected)

 

 

485 TERM jumper

Default: jumpered

None—do NOT change factory default

(connected)

 

 

EPOP jumper

Disabled

Enable to use the EPOP input

 

 

 

Audible horn

Enabled

May be disabled via the audible horn jumper

 

 

 

Manual Override switch

Off (outputs controlled by

On (Turn on all output relays)

 

programming)

 

DEFAULT SETTINGS - MODEM (FROM Table 21)

 

 

 

 

Feature

Default

Other Options

 

 

 

 

 

Any string (up to 40 characters); for international

Initialization String (InitString)

ATS0=1

dialing, add +GCI=xx, where xx is the country code

 

 

(except B5 countries—see Table 22)

Enable Modem Diagnostic Messages

N (disable)

Y (enable)

 

 

 

Modem Dial Prefix

ATE0X4DT

Any string

 

 

 

Modem Hang Up Delay After a Call

10 seconds

Any number (up to 99 seconds)

 

 

 

DIP SWITCH SETTINGS

 

 

 

 

 

Feature

Default

Other Options

 

 

 

8-position DIP switch

All are OFF (down)

May be used to reset password to factory default (see

9.9.1- Change Password)

 

 

OTHER SETTINGS

 

 

 

 

 

Feature

Default

Other Options

 

 

 

Change state of outputs - automatic

AUTO (automatic control)

Force an output ON / OFF via Manual Output Ctrl menu

or manual control

 

Force all outputs ON via hardware switch

Password

AAAA

Any 4 characters (see Table 14 for valid characters)

 

 

 

Reset common alarm with silence

N (not reset)

Y (reset with silence)

 

 

 

Battery connected

Y (connected)

N (not connected)

 

 

 

118