Falcon manual F110 Wiring, Update, Power Supply

Page 17

2 Getting Started

2.2.6 Update

Click the Update button to update the firmware installed on the selected F110. Updated firmware files provided by RLE, add new features and enhance the web browser interface. These firmware updates are available from RLE if firmware replacement is necessary.

Note When obtaining the F110 Firmware Update file from the RLE Technologies website, be sure to save the file instead of opening it from a web browser. After receiving the file, right-click the F110 Firmware Update file and select “Properties.” If the F110 Firmware Update file has a “.zip” extension, replace “.zip” with “.upd” before uploading the file with the Device Discovery Utility.

2.3.F110 Wiring

RLE recommends an 18AWG stranded copper wire for connection from each monitored point to the terminal block (TB) connection on the F110 (8 Switched Sensors inputs only). RLE recommends no more than 200 feet (60.9m) of wire at this specification. If longer runs are needed, please contact RLE for application guidance.

2.3.1 Power Supply

Plug the wall adapter into the connection labeled Power. The wall adapter has a 6 foot (18.82m) power cord. RLE recommends powering the F110 from a UPS supply to allow the F110 to send alarm notification during a power outage.

Figure 2.3 5VDC Power Supply Connection

NEVER connect main power to the sensors or sensor cables.

WARNING

www.rletech.com

17

970.484.6510

Image 17
Contents Monitoring Revision History Product Registration Rletech.com 970.484.6510 Contents Rletech.com Figures Rletech.com 970.484.6510 Tables Rletech.com Product Description System OverviewFront Panel Front Panel Indicators and ControlsF110 Terminal Block Designations Terminal Block DesignationsSystem Overview 970.484.6510 Communication InstallationGetting Started Search SettingsSet IP IP Address Assignment for Static Only NetworksPower Supply F110 WiringUpdate Physical Connection 2 RJ45 Ethernet ConnectionStatus Screen F110 WEB InterfaceF110 Web Interface Overview Authentication Security Prompt no Username or Password Settings ScreenNetwork Network SettingsEmail Settings Snmp Snmp SettingsChannel 2, Channel 3 and Channel External Temperature/HumiditySecurity Switched Sensor Alarm ConfigurationAdvanced Security SettingsRestore Defaults Prompt Reset DefaultsAbout Screen Help ScreenF110 Modbus Capabilities Modbus Configuration VIA TelnetTelnet Configuration Enable MODBUS? N? Register Name Description Units Range Modbus RegistersHexadecimal Decimal Value Description Switch Sensor 1 Alarm On 1 = Closed, 0 = Open Modbus Registers 970.484.6510 Inputs Temperature/Humidity Technical SpecificationsOperating Environment Temperature