2 Getting Started
2.2.6 Update
Click the Update button to update the firmware installed on the selected F110. Updated firmware files provided by RLE, add new features and enhance the web browser interface. These firmware updates are available from RLE if firmware replacement is necessary.
Note When obtaining the F110 Firmware Update file from the RLE Technologies website, be sure to save the file instead of opening it from a web browser. After receiving the file,
2.3.F110 Wiring
RLE recommends an 18AWG stranded copper wire for connection from each monitored point to the terminal block (TB) connection on the F110 (8 Switched Sensors inputs only). RLE recommends no more than 200 feet (60.9m) of wire at this specification. If longer runs are needed, please contact RLE for application guidance.
2.3.1 Power Supply
Plug the wall adapter into the connection labeled Power. The wall adapter has a 6 foot (18.82m) power cord. RLE recommends powering the F110 from a UPS supply to allow the F110 to send alarm notification during a power outage.
Figure 2.3 5VDC Power Supply Connection
NEVER connect main power to the sensors or sensor cables.
WARNING
www.rletech.com | 17 | 970.484.6510 |