AModbus Configuration Via Telnet

Enable MODBUS? (N)?

Enter Y to enable Modbus and N to disable it. When Modbus is disabled, the F110 will not actively listen on the Modbus TCP port for Modbus requests.

MODBUS Port: (502)

By default, the F110 listens for Modbus requests on TCP port 502. This port can be changed to any valid TCP port number although it is recommended to leave it set for port 502 to ensure compatibility with other Modbus devices on the network.

Should IP List Allow or Deny Connections (0=Allow, 1=Deny):

The F110 is configured by default to deny connections from any IP addresses listed in the Modbus IP list. When all IP addresses in this list are set to default (0.0.0.0) the F110 will deny connections from no devices. In other words, by default the F110 allows connections from all IP addresses. This can be modified if desired so that the F110 will only allow connections from IP addresses appearing in the IP list. Selecting “0=Allow” will only allow connections from the IP addresses provided in the list and deny connections from all other addresses. Selecting “1=Deny” will deny connections from all address in the list but accept from all other addresses.

Enter IP addresses for MODBUS Security:

Up to three (3) IP addresses can be specified and added to the Modbus IP list. This list can be used to either allow or deny connections if the IP address that the request originated from matches an IP address in the list. To configure IP addresses, enter each IP address when prompted or enter 0.0.0.0 to leave blank.

Save Changes And Exit

When configuration changes are complete, press 9 and Enter to save the changes and exit. The F110 will reboot and apply the new settings.

www.rletech.com

30

970.484.6510

Image 30
Contents Monitoring Revision History Product Registration Rletech.com 970.484.6510 Contents Rletech.com Figures Rletech.com 970.484.6510 Tables Rletech.com System Overview Product DescriptionFront Panel Indicators and Controls Front PanelTerminal Block Designations F110 Terminal Block DesignationsSystem Overview 970.484.6510 Installation Getting StartedCommunication Set IP SettingsSearch IP Address Assignment for Static Only NetworksF110 Wiring UpdatePower Supply 2 RJ45 Ethernet Connection Physical ConnectionF110 WEB Interface F110 Web Interface OverviewStatus Screen Settings Screen Authentication Security Prompt no Username or PasswordNetwork Settings NetworkEmail Settings Snmp Settings SnmpExternal Temperature/Humidity Channel 2, Channel 3 and ChannelSwitched Sensor Alarm Configuration SecuritySecurity Settings AdvancedReset Defaults Restore Defaults PromptHelp Screen About ScreenModbus Configuration VIA Telnet Telnet ConfigurationF110 Modbus Capabilities Enable MODBUS? N? Modbus Registers Register Name Description Units RangeHexadecimal Decimal Value Description Switch Sensor 1 Alarm On 1 = Closed, 0 = Open Modbus Registers 970.484.6510 Technical Specifications Inputs Temperature/HumidityOperating Environment Temperature