The connection should be shielded in a liquid tight or approved flexible conduit with proper conductors of correct size installed in accordance with the National Electric Code or other applicable codes. The connection must be made by a qualified electrician using the wiring diagram provided with the
Use wire sizes indicated in Table 3 through 7 for runs up to 50 feet.
Use next larger size for runs of 50 to 100 feet. Use two sizes larger for runs greater than 100 feet.
For personal safety and proper operation, the
GROUNDING INSTRUCTIONS
This appliance must be connected to a grounded metal, permanent wiring system; or an equipment- grounding conductor must be run with the circuit conductors and connected to the equipment- grounding terminal or lead on the appliance.
IMPORTANT: Alliance Laundry Systems Warranty does not cover components that fail as a result of improper input voltage.