3.Multiple Dryer (Common) Venting

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main duct at an angle not more than 45º in the direction of airflow and should be spaced at least 38-1/4 inches (97.2 cm) apart. The main duct should be tapered, with the diameter increasing before each individual duct (10- inch [25.4 cm] minimum) is added.

IMPORTANT: No more than four (4) dryers should be connected to main common duct.

The main duct may be any shape so long as the minimum cross section area is provided. The illustration on page 18 shows the minimum cross section area for multiple dryer round or square venting. These figures must be increased 10 square inches (64.52 square centimeters) when rectangular main ducting is used, and the ration of duct width to depth should not be greater than 3-1/2 to 1. These figures must be increased in proportion if the main duct run from the last dryer to where it exhausts to the outdoors is unusually long (over 15-feet [4.6 meters]) or has numerous (more than two [2] elbows in it). In calculating ductwork size, the cross section area of a square or rectangular duct must be increased twenty percent (20%) for each additional 15-feet (4.6 meters). The diameter of a round exhaust must be increased ten percent (10%) for each additional 15-feet (4.6 meters). Each 90º elbow is equivalent to an additional 30-feet (9.2 meters) and each 45º elbow is equivalent to an additional 15-feet (4.6 meters).

IMPORTANT: For extended ductwork runs, the cross section area of the ductwork can only be increased to an extent. Maximum proportional ductwork runs cannot exceed 15-feet (4.6 meters) with two (2) elbows. When the ductwork approaches the maximum

as noted in this manual, a professional heating, venting, and air conditioning (HVAC) firm should be consulted for proper venting.

The ductwork should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping into the building. Inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning of lint from the ductwork.

NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible materials, the opening must be 2-inches (2.54 cm) larger than the duct (all the way around). The duct must be centered within this opening.

a.Outside Ductwork Protection

1)To protect the outside end of the horizontal ductwork from weather, a 90º elbow bent downward should be installed where the exhaust exits the building. If the ductwork travels vertically up through the roof, it should be protected from the weather by using a 180º turn to point the opening downward. In either case, allow at least twice the diameter of the duct between the duct opening and the nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust ductwork.

17

Image 21
Contents MDG-75 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Routine Maintenance Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsPage Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Component Identification Page Location Requirements Installation ProceduresUNPACKING/SETTING UP Dryer Enclosure Requirements Fresh AIR Supply Requirements Horizontal Venting Exhaust RequirementsSingle Dryer Venting Page Page Page Electrical Requirements Electrical InformationMDG-75 Gas Page Single-Phase 1Ø Electrical Connections Leads Page Page GAS Information Type of GAS Page Page Preparation for OPERATION/START-UP Preoperational Tests Basket Coating Preoperational Instructions Shut Down Instructions SERVICE/PARTS Information ServiceParts Returning Warranty Cards Warranty InformationCleaning Routine MaintenanceLubrication AdjustmentsProcedure for Functional Check Replacement Components Page Page Timing Legend Reversing Timer SPIN/DWELL AdjustmentsData Label Data Label InformationSerial Number Microprocessor Controller Computer Models TroubleshootingBlower and fan motors are not operating does not start Failed microprocessor controller computer Failed keyboard touch pad label assembly Microprocessor controller computer L.E.D. display reads Sefl Dryer operates but is taking too long to dry GAS Models AA. Condensation on main door glass Timer Models Blower/fan motors are not operating does not start GAS Models Dryer operates but is taking too long to dry Condensation on main door glass Page P O RTA N T Manual Reset HI-LIMIT Instructions