Alarm Message | Cause | Corrective Action | Dryer Status |
|
|
|
|
VALVE MTR | The limit switch on the | Limit switch may be out of | - Dryer Shuts down: |
| valve may not have | position. | - Process blower OFF. |
| been wired correctly. | switch to make sure it trips | - Process heaters OFF. |
| The valve has made | when it is at the high | - Regen heaters OFF. |
| enough rotations and | position, and it does not | - Alarm light is ON |
| the correct position of | touch the cam when it is at | - Alarm horn is ON. |
| the valve was not | the low position. |
|
| detected. | The switch is indicating the |
|
|
| incorrect desiccant tank is in |
|
|
| regeneration. Check the |
|
|
| wiring of the switch against |
|
|
| the wiring diagram. Make |
|
|
| sure all the wire connections |
|
|
| are tight. |
|
|
| Limit switch may be faulty. |
|
|
| Replace the switch and |
|
|
| make sure the wires are |
|
|
| connected correctly. |
|
6-2 Determining Temperature Controller Errors or Sensor Errors
Using a Thermocouple
If the controller displays a temperature that is close to room temperature (70ºF/21ºC) when you
Other service problems or questions can be answered by contacting the Service Department.