American Dryer Corp ADG-78 II installation manual

Page 18

To compensate for the use of registers or louvers used over the openings, this make-up air must be increased by approximately thirty-three percent (33%). Make-up air openings should not be located in an area directly near where exhaust vents exit the building.

It is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to ALL the dryers.

EXAMPLE: For a bank of four (4) dryers, two (2) unrestricted openings measuring 2 feet by 1-1/2 feet (6 square feet) is acceptable.

Allowances must be made for remote or constricting passageways or where dryers are located at excessive altitudes or predominantly low pressure areas.

IMPORTANT: M ake-upairmust be provided from a source free of dry cleaning solvents fumes. Make-up air that is contaminated by dry cleaning solvent fumes willresult in irreparable damage the motors and other dryer components.

NOTE: Componentfailureduetodrycleaningsolventfumes wil VOID THE WARRANTY.

14

Image 18
Contents ADG-78 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Routine Maintenance Section Important InformationSafety Precautions What to do if YOU Smell GASNational Electric Code ANSI/NFPA no -LATEST Edition SPECIFICATIONS/COMPONENT Identification SpecificationsSpecifications Component Identification Page Installation Procedures Location Requirements UNPACKING/SETTING UP Bracket Before Starting the DryerDryer Enclosure Requirements Fresh AIR Supply Page Exhaust Requirements Reduced Anywhere Down Stream of the Dryer Reduced Anywhere Down Stream of the Dryer Page Electrical Information ADG-78 II Gas Page Black Positive White Neutral Green Ground Page GAS Information Type of GAS Page Page Preparation for OPERATION/START-UP Preoperational Tests Page Preoperational Instructions Shut Down InstructionsSERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsReturning Warranty Parts Page Routine Maintenance CleaningAdjustments DaysData Label LOCATION/INFORMATION Data LabelSerial Number Procedure for Functional Check Replacement Components Burner flame must shut off immediately ADC 113101 1- 09/01/99-30