American Dryer Corp ML-82 III installation manual Installation Procedures, Location Requirements

Page 12

SECTION III

INSTALLATION PROCEDURES

Installation should be performed by competent technicians in accordance with local and state codes. In the absence of these codes, the installation must conform to applicable American National Standards: ANSI Z223.1- LATEST EDITION (National Fuel Gas Code) or ANSI/NFPA NO. 70-LATEST EDITION (National Electrical Code) or in Canada, the installation must conform to applicable Canadian Standards: CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (Liquid Propane [L.P.] Gas) or LATEST EDITION (for General Installation and Gas Plumbing) or Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION (for Electrical Connections).

A. LOCATION REQUIREMENTS

Before installing the dryer, be sure the location conforms to local codes and ordinances. In the absence of such codes or ordinances the location must conform with the National Fuel Gas CodeANSI.Z223.1 LATEST EDITION, or in Canada, the installation must conform to applicable Canadian Standards: CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (L.P. Gas) or LATEST EDITION (for General Installation and Gas Plumbing).

1.The dryer must be installed on a sound level floor capable of supporting its weight. Carpeting must be removed from the floor area that the dryer is to rest on.

IMPORTANT: “The dryer must be installed on noncombustible floors only.”

2.The dryer must not be installed or stored in an area where it will be exposed to water and/or weather.

3.The dryer is for use in noncombustible locations.

4.Provisions for adequate air supply must be provided as noted in this manual (refer to Fresh Air Supply Requirements in Section D).

5.Clearance provisions must be made from combustible construction as noted in this manual (refer to Dryer Enclosure Requirements in Section C).

6.Provisions must be made for adequate clearances for servicing and for operation as noted in this manual (refer to Dryer Enclosure Requirements in Section C).

7.The dryer must be installed with a proper exhaust duct connection to the outside as noted in this manual (refer to Exhaust Requirements in Section E).

8.Dryer must be located in an area where correct exhaust venting can be achieved as noted in this manual (refer to Exhaust Requirements in Section E).

IMPORTANT: Dryer should be located where a minimum amount of exhaust duct will be necessary.

9. The dryer must be installed with adequate clearance for air openings into the combustion chamber.

CAUTION: This dryer produces combustible lint and must be exhausted to the outdoors. Every 6 months, inspect the exhaust ducting and remove any lint buildup.

8

American Dryer Corp.

113344 - 9

Image 12
Contents ML-82 III Installation Manual ML-82 For Your Safety Page Table of Contents Safety Precautions SectionStandards SPECIFICATIONS/COMPONENT Identification SpecificationsSpecifications Component Identification 113344 Installation Procedures Location RequirementsUNPACKING/SETTING UP This Exhaust Duct Transition Piece Must be Installed FirstDryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements General Exhaust Ductwork Information113344 American Dryer Corp 113344 113344 Electrical Information Electrical RequirementsGas and Steam GAS Information Type of GAS Type of GAS 113344 Operating Steam Pressure Steam Information113344 Compressed Air Pressure Air Supply Fire Suppression System Before YOU Start Check Local Codes and PermitsAmerican Dryer Corp 113344 Typical water supply Preparation for OPERATION/START-UP Preoperational Test Basket Tumbler Coating Preoperational Instructions Shutdown InstructionsSERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsAmerican Dryer Corp 113344 Routine Maintenance CleaningSuggested Cleaning Schedule Adjustments LubricationLint Drawer Removal Procedure for Functional Check Replacement Components 113344 Sectionviii Data Label InformationManual Reset Burner HI-LIMIT Instructions PhaseDual Timer ADC Part No 09/04/08