C. DRYER ENCLOSURE REQUIREMENTS

Bulkheads and partitions should be made of noncombustible material.

NOTE: Allowances must be made for opening the control door.

A40-inches (101.6 cm) for optimum opening of load door.

BThe maximum thickness of the bulkhead is 4-inches (10.16 cm). For electric dryers the maximum thickness of the bulkhead is 1-inch (2.54 cm) within 3-inches (7.62 cm) from the top of the control door.

CFor gas and electric dryers a minimum overhead clearance of 12-inches (30.48 cm) is required, providing no sprinkler is located above the dryer. For steam dryers or if a sprinkler is located above the dryer, 18-inches (45.72 cm) is required

DDryer should be positioned 12-inches (30.48 cm) away from the nearest obstruction and 24-inches (60.96 cm) is recommended for ease of installation, maintenance, and service.

E2-inch (5.08 cm) minimum is required for opening the control door.

FFlooring should be level or below dryer cabinet for ease of removing panels during maintenance.

GDryers may be positioned sidewall to sidewall, however a 1/16” (1.5875 mm) minimum allowance must be made for the opening and closing of the control door, along with the removal of panels during maintenance.

10

American Dryer Corp.

113344 - 9

Image 14
Contents ML-82 III Installation Manual ML-82 For Your Safety Page Table of Contents Safety Precautions SectionStandards SPECIFICATIONS/COMPONENT Identification SpecificationsSpecifications Component Identification 113344 Installation Procedures Location RequirementsUNPACKING/SETTING UP This Exhaust Duct Transition Piece Must be Installed FirstDryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements General Exhaust Ductwork Information113344 American Dryer Corp 113344 113344 Electrical Information Electrical RequirementsGas and Steam GAS Information Type of GAS Type of GAS 113344 Operating Steam Pressure Steam Information113344 Compressed Air Pressure Air Supply Fire Suppression System Before YOU Start Check Local Codes and PermitsAmerican Dryer Corp 113344 Typical water supply Preparation for OPERATION/START-UP Preoperational Test Basket Tumbler Coating Preoperational Instructions Shutdown InstructionsParts SERVICE/PARTS InformationService Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsAmerican Dryer Corp 113344 Suggested Cleaning Schedule Routine MaintenanceCleaning Adjustments LubricationLint Drawer Removal Procedure for Functional Check Replacement Components 113344 Sectionviii Data Label InformationDual Timer Manual Reset Burner HI-LIMIT InstructionsPhase ADC Part No 09/04/08