D. FRESH AIR SUPPLY REQUIREMENTS

When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail switch “fluttering” problems may result, as well as premature motor failure from overheating.

Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An unrestricted source of air is necessary for each dryer. An airflow of 1,700 cfm (48.14 cmm) must be supplied to each dryer. As a general rule, an unrestricted air entrance from the outdoors (atmosphere) of a minimum of 2-1/2 square feet (0.23 square meters) is required for each dryer. The dryer must be installed with provisions for adequate combustion and make-up air supply.

To compensate for the use of registers or louvers used over the openings, the area must be increased by approximately thirty-three percent (33%). Make-up air openings should not be located in an area directly near where exhaust vents exit the building.

It is not necessary to have separate make-up air openings for each dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to ALL the dryers.

EXAMPLE: For a bank of four (4) dryers, two (2) unrestricted openings measuring 2-1/2 feet by 2 feet (0.76 meters by 0.61 meters) are acceptable.

Allowances must be made for remote or constricting passageways or where dryers are located at excessive altitudes or predominantly low pressure areas.

IMPORTANT: Make-up air must be provided from a source free of dry cleaning solvent fumes. Make-up air that is contaminated by dry cleaning solvent fumes will result in irreparable damage to the motors and other dryer components.

NOTE: Component failure due to dry cleaning solvent fumes will VOID THE WARRANTY.

113344 - 9

www.amdry.com

11

Image 15
Contents ML-82 III Installation Manual ML-82 For Your Safety Page Table of Contents Section Safety PrecautionsStandards Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Component Identification 113344 Location Requirements Installation ProceduresThis Exhaust Duct Transition Piece Must be Installed First UNPACKING/SETTING UPDryer Enclosure Requirements Fresh AIR Supply Requirements General Exhaust Ductwork Information Exhaust Requirements113344 American Dryer Corp 113344 113344 Electrical Requirements Electrical InformationGas and Steam GAS Information Type of GAS Type of GAS 113344 Steam Information Operating Steam Pressure113344 Compressed Air Pressure Air Supply Before YOU Start Check Local Codes and Permits Fire Suppression SystemAmerican Dryer Corp 113344 Typical water supply Preparation for OPERATION/START-UP Preoperational Test Basket Tumbler Coating Shutdown Instructions Preoperational InstructionsSERVICE/PARTS Information ServiceParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyAmerican Dryer Corp 113344 Routine Maintenance CleaningSuggested Cleaning Schedule Lubrication AdjustmentsLint Drawer Removal Procedure for Functional Check Replacement Components 113344 Data Label Information SectionviiiManual Reset Burner HI-LIMIT Instructions PhaseDual Timer ADC Part No 09/04/08