American Dryer Corp ML-82 III installation manual 113344

Page 27

c.Flexible hoses or couplings must be used. The dryer vibrates slightly when it runs and this will cause the steam coil connections to crack if they are hard piped to the supply and return mains.

d.Shutoff valves for each dryer should be installed in the supply, return, and drip trap return lines. This will allow the dryer to be isolated from the supply and return mains if the dryer needs maintenance work.

e.Install an inverted bucket steam trap and check valve for each unit at least 12-inches (30.48 cm) below steam coil as close to the coil as possible; a trap with a capacity of 1,000 lb (454 kg) of condensate per hour at 125 psi (8.62 bar) is needed for each unit.

f.A 3/4-inch (19.05 mm) vacuum breaker should be installed for each unit in the piping. This will prevent the condensing steam from causing a vacuum inside the coil and possibly damaging the coil.

g.The supply and return lines should be insulated. This will save energy and provide for the safety of the operator and maintenance personnel.

h.Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch (6.35 mm) for every 1 foot (0.30 meters) back toward the steam supply header causing any condensate in the line to drain to the header. Install a bypass trap in any low point to eliminate wet steam.

IMPORTANT: Flexible hose and couplings must be used. Coil failure due to hard plumbing connections will VOID THE WARRANTY.

3.Steam Damper Air System Connections

The dryer is manufactured with a pneumatic (piston) damper system, which requires an external supply of compressed air. The air connection is made to the steam damper solenoid valve, which is located at the rear inner top area of the dryer just above the electric service relay box.

113344 - 9

www.amdry.com

23

Image 27
Contents ML-82 III Installation Manual ML-82 For Your Safety Page Table of Contents Section Safety PrecautionsStandards Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Component Identification 113344 Location Requirements Installation ProceduresThis Exhaust Duct Transition Piece Must be Installed First UNPACKING/SETTING UPDryer Enclosure Requirements Fresh AIR Supply Requirements General Exhaust Ductwork Information Exhaust Requirements113344 American Dryer Corp 113344 113344 Electrical Requirements Electrical InformationGas and Steam GAS Information Type of GAS Type of GAS 113344 Steam Information Operating Steam Pressure113344 Compressed Air Pressure Air Supply Before YOU Start Check Local Codes and Permits Fire Suppression SystemAmerican Dryer Corp 113344 Typical water supply Preparation for OPERATION/START-UP Preoperational Test Basket Tumbler Coating Shutdown Instructions Preoperational InstructionsSERVICE/PARTS Information ServiceParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyAmerican Dryer Corp 113344 Routine Maintenance CleaningSuggested Cleaning Schedule Lubrication AdjustmentsLint Drawer Removal Procedure for Functional Check Replacement Components 113344 Data Label Information SectionviiiManual Reset Burner HI-LIMIT Instructions PhaseDual Timer ADC Part No 09/04/08