American Dryer Corp AD-120ES II installation manual

Page 24

The main duct may be any shape or cross-sectional area, so long as the minimum cross section area is provided. The illustrations on page 21 show the minimum cross section area for multiple dryer round or square venting. These figures must be increased 10 square inches (64.51 square centimeters) when rectangular main ducting is used, and the ratio of duct width to depth should not be greater than 3-1/2 to 1. These figures must be increased in proportion if the main duct run to the last dryer to where it exhausts to the outdoors is unusually long (over 20 feet [6.09 meters]) or has numerous elbows (more than two [2]) in it. In calculating ductwork size, the cross section area of a square or rectangular duct must be increased twenty percent (20%) for each additional 20 feet (6.09 meters). The diameter of a round exhaust must be increased ten percent (10%) for each additional 20 feet (6.09 meters). Each 90° elbow is equivalent to an additional 15 feet (4.57 meters).

IMPORTANT: For extended ductwork runs, the cross section area of the ductwork can only be increased to an extent. Maximum proportional ductwork runs cannot exceed

20 feet (6.09 meters) more than the original limitations of 20 feet (6.09 meters) with two (2) elbows. When the ductwork approaches the maximum limits as noted in this manual, a professional heating, venting, and air conditioning (HVAC) firm should be consulted for proper venting information.

IMPORTANT: Exhaust back pressure measured by a manometer at each dryer exhaust duct area must be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column (W.C.).

The duct should be smooth inside with no projections from sheet metal screws or other obstructions, which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping into the building. Inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning of lint from the ductwork.

NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct must be centered within this opening.

a.Outside Ductwork Protection

1)To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward should be installed where the exhaust exits the building. If the exhaust ductwork travels vertically up through the roof, it should be protected from the weather by using a 180° turn to point the opening downward. In either case, allow at least twice the diameter of the duct between the duct opening and nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust ductwork.

20

Image 24
Contents AD-120ES Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Cleaning Adjustments Lubrication Data LabelImportant Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASStandards SPECIFICATIONS/COMPONENT Identification SpecificationsADG-120ES ADE-120ES ADS-120ES Component Identification Page Installation Procedures Location RequirementsUNPACKING/SETTING UP Page This Exhaust Duct Transition Piece Must be Installed First Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Downstream of Dryer Page Page Page Electrical Information Electrical Service Specifications PER Dryer ADE-120 II 72 Kw Electric Reversing, 3ø ADE-120 II 80 Kw Electric Reversing, 3ø Page Page GAS Information Type of GAS Page Page Steam Information 862.84 kPa689.47 kPa 204 kg/hrPage Bars Page Preparation for Operation Preoperational Tests Inches 26.1 mb water column Shut Down Instructions Basket CoatingOperating Instructions SERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsWarranty Returning Warranty PartsPage Routine Maintenance CleaningSuggested Cleaning Schedule Steam Dryers Adjustments LubricationTroubleshooting Drive motor is not operating does not startBlower motor is not operating does not start Microprocessor controller computer display reads dSFL Microprocessor controller computer display reads doorFailed 24 VAC transformer No heat for Steam Models only No heat for Electric Models onlyDryer operates but is taking too long to dry Condensation on main door glassDryer is making scraping noise at basket tumbler area Excessive noise and/or vibrationDrive motor only is not operating does not start GAS ModelsElectric Models Dryer operates but is taking too long to dry load Failed hi-limit thermostat for GAS and Electric Models onlyCondensation on main door glass Data Label Information Data LabelSerial Number Reversing Timer SPIN/DWELL Adjustments Timing LegendProcedure for Functional Check Replacement Components Page Page P O R T a N T ADC P/N114501 ADC 02/07/01-25 02/12/01-25 04/06/01-25 06/27/01-25