Page 42

2)The dryer is equipped with a Direct Spark Ignition (DSI) system, which has internal diagnostics. If ignition is not established after the first attempt, the heat circuit DSI module will “LOCKOUT” until it is manually reset. To reset the DSI system, open and close main door and restart dryer (press the “ENTER/START” key).

NOTE: During the purging period, check to be sure that ALL gas shutoff valves are open.

3)Once ignition is established, a gas pressure test should be taken at the gas valve pressure tap of each dryer to assure that the water column (W.C.) pressure is correct and consistent.

NOTE: Water column pressure requirements (measured at the gas valve pressure tap)...

Natural Gas -------------------

3.5 inches (8.7 mb) water column.

Liquid Propane (L.P.) Gas ----

10.5 inches (26.1 mb) water column.

IMPORTANT: There is no regulator provided in an L.P. dryer. The water column pressure must be regulated at the source (L.P. tank) or an external regulator must be added to each dryer.

b.Electric Models

1)Check the oven contactors to insure that the electric oven is cycling properly.

c.Steam Models

1)Check to insure that steam damper is functioning properly.

a)The steam damper should not “slam” (open/closed) when it reaches the end of (piston) travel. Additionally, the steam damper should not bind or stop during travel. If either of these conditions occur, the flow control must be adjusted. (Refer to the Cool Down Mode in top illustration on page 35 for air adjustment instructions.)

6.Make a complete operational check of ALL safety-related circuits (i.e., lint drawer switch and sail switch on gas models).

NOTE: To check for proper sail switch operation, open the main door and while holding main door switch plunger in, start dryer. Dryer should start but heat circuit should not be activated (on). If heat (burner) does activate, shut the dryer off and make necessary adjustments.

7.A reversing basket (tumbler) dryer should never be operated with less than a 60 lb (27 kg) load (dry weight). The size of the load will affect the coast-down and dwell (stop) times. The basket (tumbler) must come to a complete stop before starting in the opposite direction.

a. Microprocessor Controller (Computer) Dryer Models

1)Spin and stop times are not adjustable in the Automatic Mode and have been preprogrammed into the microprocessor controller (computer) for a 120-second spin time and a 5-second dwell (stop) time.

2)Spin and stop times are adjustable in the Manual (Timed) Mode.

38

Image 42
Contents AD-120ES Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Cleaning Adjustments Lubrication Data LabelImportant Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASStandards SPECIFICATIONS/COMPONENT Identification SpecificationsADG-120ES ADE-120ES ADS-120ES Component Identification Page Installation Procedures Location RequirementsUNPACKING/SETTING UP Page This Exhaust Duct Transition Piece Must be Installed First Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Downstream of Dryer Page Page Page Electrical Information Electrical Service Specifications PER Dryer ADE-120 II 72 Kw Electric Reversing, 3ø ADE-120 II 80 Kw Electric Reversing, 3ø Page Page GAS Information Type of GAS Page Page 689.47 kPa Steam Information862.84 kPa 204 kg/hrPage Bars Page Preparation for Operation Preoperational Tests Inches 26.1 mb water column Shut Down Instructions Basket CoatingOperating Instructions SERVICE/PARTS Information ServiceParts Warranty Warranty InformationReturning Warranty Cards Returning Warranty PartsPage Routine Maintenance CleaningSuggested Cleaning Schedule Steam Dryers Adjustments LubricationTroubleshooting Drive motor is not operating does not startBlower motor is not operating does not start Microprocessor controller computer display reads dSFL Microprocessor controller computer display reads doorFailed 24 VAC transformer No heat for Steam Models only No heat for Electric Models onlyDryer operates but is taking too long to dry Condensation on main door glassDryer is making scraping noise at basket tumbler area Excessive noise and/or vibrationDrive motor only is not operating does not start GAS ModelsElectric Models Dryer operates but is taking too long to dry load Failed hi-limit thermostat for GAS and Electric Models onlyCondensation on main door glass Data Label Information Data LabelSerial Number Reversing Timer SPIN/DWELL Adjustments Timing LegendProcedure for Functional Check Replacement Components Page Page P O R T a N T ADC P/N114501 ADC 02/07/01-25 02/12/01-25 04/06/01-25 06/27/01-25