Maytag MDG-30 manual

Page 30

Consistent gas pressure is essential at ALL gas connections. It is recommended that a 3/4-inch pipe gas

loop be installed in the supply line serving a bank of dryers. An in-line pressure regulator must be installed in the gas supply line (header) if the (natural) gas pressure exceeds 12.0 inches of water column pressure. Refer to the illustrations on the previous page (page 25).

NOTE: A water column test pressure of 3.5 inches for natural gas and 10.5 inches for L.P. (liquid propane) dryers is required at the gas valve pressure tap of each dryer for proper and safe operation.

A 1/8" N.P.T. plugged tap, accessible for a test gauge connection, must be installed in the main gas supply line immediately upstream of each dryer.

IMPORTANT: Pipe joint compounds that resist the action of natural gas and L.P. gas must be used.

IMPORTANT: Test ALL connections for leaks by brushing on a soapy water solution (liquid detergent works well).

WARNING: NEVER TEST FOR LEAKS WITH A FLAME!

ALL components and materials must conform to National or Canadian Gas Code specifications. It is important that gas pressure regulators meet applicable pressure requirements and that gas meters be rated for the total amount of ALL the appliance BTU's being supplied.

IMPORTANT: The dryer and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

NOTE: The dryer must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure test of the gas supply system at test pressures equal to or less than 1/2 psig (3.5 kPa).

26

Image 30
Contents MDG-30 Fast Dry Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Technical Information Section Safety Precautions Personal Injury or Fire could ResultADJUSTING, INSTALLATION, or Testing Ofany Equipment per Osha Occupational Safety and HealthAdministration StandardsGAS Supply Before ANY Covers or Guards are Removed Specifications SuperSpecifications MDG-30 Fast Dry Installation Procedures Location Requirements Dryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Single Dryer Venting Illus. B Multiple Dryer Common Venting ILLUS. D Importantventingreminders Electrical Information Electrical RequirementsMust be Provided Odfn Klwh Uhhq Important a Circuit Serving Each Dryer Must be Provided DG-30 Fast DRY GAS GAS Information Injury and Improper Operation of the Dryer$785$ Page Page Preparation for Operation and START-UP Preoperational Tests GAS Models onlyPreoperational Instructions Page OPL Models Shut Down Instructions Service PartsReturning Warranty Cards SectionRoutine Maintenance CleaningAdjustments LubricationNo L.E.D. light emitting diode display Drive motor not operating does not startBlower motor not operating does not start Microprocessor computer display reads dSFLMicroprocessor controller computer display reads door No heat, ignitor sparks, burner goes on and off right awayDryer operates but is taking too long to dry Condensation on main door glass Dryer or scraping noise at basket tumbler areaExcessive noise or vibration Heating unit not operating ALL temperature selections Main burners are burning with a yellow flameDryer operates but is taking too long to dry load Dryer is cycling on hi-limit thermostat Technical Information Data LabelSerial Number Procedure for Functional Check Replacement Components Direct Spark Ignition DSI System MAYTAG-113069 1-01/29/99-250