E6581315

4.2. Commands

Here are the communication commands available.

Command

Function

R command

Reads the data with the specified communication number.

W command

Writes the data with the specified communication number. (RAM and EEPROM).

P command

Writes the data with the specified communication number. (RAM).

G command

Reads the data with the specified communication number. (For binary mode only.

Dummy data is required for this command.)

 

X command

Block communication (Computer -> Inverter)

Y command

Block communication (Inverter -> Computer)

„W (57H) (RAM*1 /EEPROM*2 write)

This command is used to write new data into the parameter specified using it communication num- ber. It writes data into the RAM and EEPROM. For parameters whose settings cannot be stored in the EEPROM (e.g., parameter with the communication number FA00), the W (57H) command writes data into the RAM only. It cannot be used to write data into read-only parameters (e.g., parameter with the communication number FD?? or FE??).

Each time an attempt to write data is made, the inverter checks if the data falls within the specified range. If this check reveals that the data falls outside the specified range, the inverter will reject it and return an error code.

- Ex.: Setting the deceleration time (communication number: 0010) to 10 sec.

<ASCII mode>

 

CR: Carriage return

Computer Inverter

Inverter Computer

 

(W00100064)CR

(W00100064)CR

…(100.1=100=0064H)

<Binary mode>

 

 

Computer Inverter

Inverter Computer

 

2F 57 00 10 00 64 FA

2F 57 00 10 00 64 FA

…(100.1=100=0064H)

Notice

Do not write the same parameter to the EEPROM more than 10,000 times. The life time of EEPROM is approximately 10,000 times.(Some parameters are not limited, please refer to the “9.Parameter data “) The lifetime of EEPROM is approximately 10,000 times. When using the TOSHIBA inverter protocol and the data does not need to be records, use P command (the data is written only to RAM).

„Explanation of terms

*1: The RAM is used to temporarily store inverter operation data. Data stored in the RAM is cleared when the inverter is turned off, and data stored in the EEPROM is copied to the RAM when the inverter is turned back on.

*2: The EEPROM is used to store inverter operation parameter settings, and so on. Data stored in the EEPROM is retained even after the power is turned off, and it is copied to the RAM when the inverter is turned on or reset.

17

Image 18
Contents Tosvert VF-AS1 Series RS485 Communication Function E6581315②Read first Safety precautions E6581315Contents General outlines of the communication function BIT15 BIT8BIT7 BIT0Bit Word Data transmission specifications BIT2Communication protocol About the handling of received framesMOUBUS-RTU Binary mode 2FH Toshiba Inverter ProtocolINV-NO CMD Data transmission format used in Ascii modeData transmission format Data5bytes Blank 28H Bytes Checksum areaINV-NO Data SUMData transmission format used in binary mode Byte Bytes Command receivedReturned for the 57H W and 50H P commands Sum 1 bytes Checksum not omissible 00H to FFHNorn 2FH Byte 4EH6EH BytesTransmission format of Block Communication Page Bytes Blank Start Code INV-NO Reads the data with the specified communication number CommandsDummy data is required for this command Block communication Computer InverterRFE03CR RFE03077BCRPage Transmission errors Format error Data transmission format does not matchCommunication There is no communication number that matches Broadcast communication function VF-AS1 From the computer H = 24d  trip status Examples of the use of communication commandsAscii mode Computer → Inverter Inverter → Computer RFC90CRExamples of Communication programs Input #1,B$ =LENS$ For I=1 to LNext Goto160 T=TIMER COUNT=TIMER-T If Count 0 then T=TIMERPrint #1,B$ Page End If MSComm1.Output = Text2.Text & Chr13 End SubText2.Text = Text1.Text = End Sub MODBUS-RTU protocol Inverter number Read command MODBUS-RTU transmission formatCRC 5bytes Blank Command 1 byte Write commandBlank Command 1 byte Text size is 8 bytes fixed InverterBit counter = Error codesCRC Generation End Return CRCInter-drive communication E6581315 QWiring 2-wire RS485 communication Never use pin-7 P11 QWiring 4-wire RS485 communication)Page Parameters relating to the slave side example Proportional control of speed =0.01%Slave 100.00Hz1 00% Slave 100.00Hz 00%90.00Hz 45.00Hz 80.00Hz 40.00HzTransmission format for inter-drive communication INV-NO 1 byte Inverter numberCommunication parameters 0OFFMODBUS-RTU Baud rate,  , Parity  Inverter numberMaster INV To Slave „ Timer Time-out period Computer linkPC → INV INV INV → PC PC → INVSend waiting time ,  Free notesUse this function for the following case PI OFF Commands and monitoring from the computerCommunication commands commands from the computer OFFBrake release B Electric Power quantityForcibly braked Preliminary excitation Braking answer BAWire RS485 communication FA32 „ AM analog output FA52 „ Terminal board output data FA50„ FM analog output FA51 Output terminal no Specified data outputMonitoring from the computer RFD00CRUnit 0.01% N·m Input terminal function selection 9 f119 „ Input terminal board status FD06, FE06RES BIT15„ Output terminal board status FD07, FE07 „ Inverter operating status 1 FD01, FE01 ST=ON ST=OFF„ Inverter operating status 2 FD42, FE42 „ Inverter operating status 3 FD49, FE49„ Inverter operating command mode status FD45, FE45 „ Inverter operating frequency mode status FD46, FE46Preset speed operation „ Alarm information monitor FC91 „ Cumulative operation time alarm monitor FE79Bit Specifications Remarks E6581315 „ Inverter model capacity code FB05 Model DataLED setting by communication Parameter Name Range SettingUtilizing panel LEDs and keys by communication „ Block Communication Function for LED Display Ascii LED display data code 00H-1FH are blank BlankKey utilization by communication FA10=0FA10=1 Parameter data EEP ROMPage FE19 Torque command Alarm codeFE02 Frequency command value 01Hz FE29 Input powerTion FE80 Cumulative power on time E6581315 FD50 Light-load high-speed torque 01%FE84 Binary input value option SUB Appendix 1 Table of data codesCan ESCAppendix 2 Response time Response time „ Data transmission timeAppendix 3 Compatibility with the communication function VF-A7Appendix 4 Troubleshooting Appendix 5 Connecting for RS485 communication TXA RXARXB TXB