Toshiba TOSVERT VF-AS1 instruction manual

Page 36

efesotomasyon.com -Toshiba inverter,drive,servo,plc

E6581315

„Setting of parameter

●Protocol selection (, ) Shipment setting: 0 (TOSHIBA)

Protocol setting with all inverters (both master and slave inverters) engaged in inter-drive commu- nication

0: Set the TOSHIBA.

*Inter-drive communication are disabled when the MODBUS-RTU protocol is selected.

*This parameter is validated after resetting the inverter or rebooting the power supply.

Setting of master and slave inverters for communication between inverters (setting of master and slave) (, ) ... Shipment setting = 

Assign one master inverter in the network. Other inverters should be the slave inverters. *Specify only one inverter as the master. In case two or more inverters are designated for the master inverter in the same network, data will collide.

-Setting to the master inverter

Set data desired for sending from the master side to the slave side. : Master (sends a frequency command)

: Master (sends an output frequency)

: Master (sends a torque command)

: Master (sends an output torque command)

- Setting to the slave inverters

Set the desired action on the slave side that will be needed when the master trips.

0: Slave (issues a 0Hz command if something goes wrong with the master) (when f806 and f826 are set to 3 and 4, respectively.))

(The output frequency is limited to the lower limit frequency.)

1: Slave (continues operation if something goes wrong with the master)

Note: If the master inverter trips when an output frequency is specified for it, the operation fre- quency of the slave inverters become 0Hz because tripping of the master inverter causes its output frequency to drop to 0Hz.

2: Slave (trips for emergency stop if something goes wrong with the master)

The way they make an emergency stop depends on the setting of f603 (emergency stop).

*This parameter is validated after resetting the inverter or rebooting the power supply.

Send waiting time () ... Shipment setting = 

-Setting to the master inverter

Specify a waiting time if you want the master to issue commands to slaves with a given delay.

Frequency setting mode selection 1 (fm0d) ・・・ Shipment setting = 2: RR/S4 input Designate a target of speed command input for the inverter to the parameter .

- Setting to the master inverter

Select an option other than RS485 communication (fm0d5 or 6).

-Setting to the slave inverters Select from between:

fm0d=5: 2-wire RS485 communication input

fm0d=6: 4-wire RS485 communication input

35

Image 36
Contents Tosvert VF-AS1 Series RS485 Communication Function E6581315②Read first Safety precautions E6581315Contents General outlines of the communication function BIT15 BIT8BIT7 BIT0Bit Word Data transmission specifications BIT2Communication protocol About the handling of received framesMOUBUS-RTU Binary mode 2FH Toshiba Inverter ProtocolData transmission format used in Ascii mode Data transmission formatINV-NO CMD Data5bytes Blank 28H Bytes Checksum areaINV-NO Data SUMData transmission format used in binary mode Command received Returned for the 57H W and 50H P commandsByte Bytes Sum 1 bytes Checksum not omissible 00H to FFHNorn 2FH Byte 4EH6EH BytesTransmission format of Block Communication Page Bytes Blank Start Code INV-NO Commands Dummy data is required for this commandReads the data with the specified communication number Block communication Computer InverterRFE03CR RFE03077BCRPage Transmission errors Format error Data transmission format does not matchCommunication There is no communication number that matches Broadcast communication function VF-AS1 Examples of the use of communication commands Ascii mode Computer → Inverter Inverter → ComputerFrom the computer H = 24d  trip status RFC90CRExamples of Communication programs =LENS$ For I=1 to L NextInput #1,B$ Goto160 T=TIMER COUNT=TIMER-T If Count 0 then T=TIMERPrint #1,B$ Page End If MSComm1.Output = Text2.Text & Chr13 End SubText2.Text = Text1.Text = End Sub MODBUS-RTU protocol Inverter number Read command MODBUS-RTU transmission formatCRC Write command Blank Command 1 byte5bytes Blank Command 1 byte Text size is 8 bytes fixed Inverter Error codes CRC Generation Bit counter = End Return CRCInter-drive communication E6581315 QWiring 2-wire RS485 communication Never use pin-7 P11 QWiring 4-wire RS485 communication)Page Parameters relating to the slave side example Proportional control of speed =0.01%Slave 100.00Hz 00% 90.00Hz 45.00HzSlave 100.00Hz1 00% 80.00Hz 40.00HzTransmission format for inter-drive communication INV-NO 1 byte Inverter numberCommunication parameters 0OFFMODBUS-RTU Baud rate,  , Parity  Inverter number„ Timer Time-out period Computer link PC → INVMaster INV To Slave INV INV → PC PC → INVSend waiting time ,  Free notesUse this function for the following case Commands and monitoring from the computer Communication commands commands from the computerPI OFF OFFElectric Power quantity Forcibly braked Preliminary excitationBrake release B Braking answer BAWire RS485 communication FA32 „ Terminal board output data FA50 „ FM analog output FA51„ AM analog output FA52 Output terminal no Specified data outputMonitoring from the computer RFD00CRUnit 0.01% N·m „ Input terminal board status FD06, FE06 RESInput terminal function selection 9 f119 BIT15„ Output terminal board status FD07, FE07 „ Inverter operating status 1 FD01, FE01 ST=ON ST=OFF„ Inverter operating status 2 FD42, FE42 „ Inverter operating status 3 FD49, FE49„ Inverter operating command mode status FD45, FE45 „ Inverter operating frequency mode status FD46, FE46Preset speed operation „ Alarm information monitor FC91 „ Cumulative operation time alarm monitor FE79Bit Specifications Remarks E6581315 „ Inverter model capacity code FB05 Model DataLED setting by communication Parameter Name Range SettingUtilizing panel LEDs and keys by communication „ Block Communication Function for LED Display Ascii LED display data code 00H-1FH are blank BlankKey utilization by communication FA10=0FA10=1 Parameter data EEP ROMPage Alarm code FE02 Frequency command value 01HzFE19 Torque command FE29 Input powerTion FE80 Cumulative power on time E6581315 FD50 Light-load high-speed torque 01%FE84 Binary input value option Appendix 1 Table of data codes CanSUB ESCAppendix 2 Response time Response time „ Data transmission timeAppendix 3 Compatibility with the communication function VF-A7Appendix 4 Troubleshooting Appendix 5 Connecting for RS485 communication RXA RXBTXA TXB
Related manuals
Manual 326 pages 49.22 Kb Manual 10 pages 12.86 Kb