8.3.2.Key utilization by communication

The VF-AS1 can use the panel keys on the inverters through external communication.

„Key Monitoring Procedure

Set panel key selection (Communication Number: FA10) to “1” to set the external key mode. How- ever, if communication duration is less than 1sec to avoid an inverter operation shutdown in com- munication disruption, communication must always be maintained, such as monitoring key data and LED data to automatically reset inverter operations to inverter key operation (FA10 = 0). Set to the external communication key mode (FA10 = 1) to disable the key function of the inverters so that in- verter operation will not be affected by pressing of the keys on the inverters. By monitoring key in- formation, which is input by the keys on the inverters in this condition, through inverter key data (Communication Number; FC01), the keys on the inverters can be operated through a controller and other devices.

*When the key mode is the external key mode, key operation as an inverter function is disabled and the inverters cannot be stopped by pressing the STOP key to stop inverter operation. Enable emergency stop through an external terminal or other device when an inverter stop is desired.

Panel Key Selection (Communication Number:FA10)

The panel key selection parameter (Communication Number; FA10) discriminates which keys are to be used, panel keys on the inverters or keys sent by external communication, as panel keys used in panel processing of the inverters.

Communication No.FC01

 

 

 

 

 

Panel key data of inverters

FA10=”0”

 

 

 

 

 

 

Communication No.FA11

FA10=”1”

 

External communication

 

 

key data

 

 

 

 

 

Communication No.FC00

Key data for inverter control panel processing

Keys on inverters enabled (Communication Number; FA10 = 0):

Key data: Data of keys on inverters (Communication Number : FC01)

Bit7

Bit6

Bit5

Bit4

Bit3

Bit2

Bit1

Bit0

KPP

EASY

ENT

MODE

DOWN

UP

STOP

RUN

“KPP” for Bit 7 indicates that panel keys are mounted on the inverters.

External keys enabled (Communication Number; FA10 = 1):

Key data: External key data (Communication Number: FA11)

 

Bit7

Bit6

Bit5

Bit4

Bit3

Bit2

Bit1

Bit0

 

-

EASY

ENT

MODE

DOWN

UP

STOP

RUN

Key monitoring (Communication Number : FC00):

 

 

 

 

Information of the enabled keys on the inverters can be monitored.

 

 

 

 

 

 

 

 

 

 

 

 

Bit7

Bit6

Bit5

Bit4

Bit3

Bit2

Bit1

Bit0

 

KPP

EASY

ENT

MODE

DOWN

UP

STOP

RUN

“KPP” for Bit 7 indicates that panel keys are enabled on the inverters.

61

Image 62
Contents Tosvert VF-AS1 Series RS485 Communication Function E6581315②Read first Safety precautions E6581315Contents Bit Word General outlines of the communication functionBIT15 BIT8BIT7 BIT0 Data transmission specifications BIT2MOUBUS-RTU Communication protocolAbout the handling of received frames Binary mode 2FH Toshiba Inverter ProtocolINV-NO CMD Data transmission format used in Ascii modeData transmission format Data5bytes Blank 28H Bytes Checksum areaINV-NO Data SUMData transmission format used in binary mode Byte Bytes Command receivedReturned for the 57H W and 50H P commands Sum 1 bytes Checksum not omissible 00H to FFHNorn 2FH Byte 4EH6EH BytesTransmission format of Block Communication Page Bytes Blank Start Code INV-NO Reads the data with the specified communication number CommandsDummy data is required for this command Block communication Computer InverterRFE03CR RFE03077BCRPage Communication There is no communication number that matches Transmission errorsFormat error Data transmission format does not match Broadcast communication function VF-AS1 From the computer H = 24d  trip status Examples of the use of communication commandsAscii mode Computer → Inverter Inverter → Computer RFC90CRExamples of Communication programs Input #1,B$ =LENS$ For I=1 to LNext GotoPrint #1,B$ 160 T=TIMER COUNT=TIMER-TIf Count 0 then T=TIMER Page Text2.Text = Text1.Text = End Sub End IfMSComm1.Output = Text2.Text & Chr13 End Sub MODBUS-RTU protocol Inverter number CRC Read commandMODBUS-RTU transmission format 5bytes Blank Command 1 byte Write commandBlank Command 1 byte Text size is 8 bytes fixed InverterBit counter = Error codesCRC Generation End Return CRCInter-drive communication E6581315 QWiring 2-wire RS485 communication Never use pin-7 P11 QWiring 4-wire RS485 communication)Page Parameters relating to the slave side example Proportional control of speed =0.01%Slave 100.00Hz1 00% Slave 100.00Hz 00%90.00Hz 45.00Hz 80.00Hz 40.00HzTransmission format for inter-drive communication INV-NO 1 byte Inverter numberCommunication parameters 0OFFMODBUS-RTU Baud rate,  , Parity  Inverter numberMaster INV To Slave „ Timer Time-out period Computer linkPC → INV INV INV → PC PC → INVUse this function for the following case Send waiting time , Free notes PI OFF Commands and monitoring from the computerCommunication commands commands from the computer OFFBrake release B Electric Power quantityForcibly braked Preliminary excitation Braking answer BAWire RS485 communication FA32 „ AM analog output FA52 „ Terminal board output data FA50„ FM analog output FA51 Output terminal no Specified data outputUnit 0.01% N·m Monitoring from the computerRFD00CR Input terminal function selection 9 f119 „ Input terminal board status FD06, FE06RES BIT15„ Output terminal board status FD07, FE07 „ Inverter operating status 1 FD01, FE01 ST=ON ST=OFF„ Inverter operating status 2 FD42, FE42 „ Inverter operating status 3 FD49, FE49Preset speed operation „ Inverter operating command mode status FD45, FE45„ Inverter operating frequency mode status FD46, FE46 Bit Specifications Remarks „ Alarm information monitor FC91„ Cumulative operation time alarm monitor FE79 E6581315 „ Inverter model capacity code FB05 Model DataUtilizing panel LEDs and keys by communication LED setting by communicationParameter Name Range Setting „ Block Communication Function for LED Display Ascii LED display data code 00H-1FH are blank BlankFA10=1 Key utilization by communicationFA10=0 Parameter data EEP ROMPage FE19 Torque command Alarm codeFE02 Frequency command value 01Hz FE29 Input powerFE84 Binary input value option Tion FE80 Cumulative power on timeE6581315 FD50 Light-load high-speed torque 01% SUB Appendix 1 Table of data codesCan ESCAppendix 2 Response time Response time „ Data transmission timeAppendix 3 Compatibility with the communication function VF-A7Appendix 4 Troubleshooting Appendix 5 Connecting for RS485 communication TXA RXARXB TXB