When Command “s” (lowercase letter) is received, the slave side judges that the master side is tripped and operates in accordance with the
For detail, see "7. Communication parameters ".
- Examples: 50% frequency command
(If maximum frequency = Frequency for operation at 80Hz = 40Hz: 50% = 5000d = 1388H)
<Binary mode> |
|
Master inverter → Slave inverter | Slave inverter → Master inverter |
2F 53 FA 01 13 88 18 | No return |
X(58H)/Y (59H) (Block Communication Command)
Data selected in the block communication write parameters (,) is written in the RAM. When returning data, data selected in block communication read parameters ( to ) is read and is returned.
For detail, see "4.1.3. Transmission format of Block Communication ".
- Examples: 60Hz operation command from communication and monitoring (Monitoring when al- ready operating at 60Hz)
(Parameter Setting: = , = , = , = , = , = , = )
<Binary mode> |
|
Computer → Inverter | Inverter → Computer |
2F 58 02 05 C4 00 17 70 D9 | 2F 59 05 00 64 00 17 70 1A 8A 24 FD 00 00 3D |