7.3.Communication
The timer function is mainly used to detect a break in a cable during communication, and if no data is sent to an inverter within the preset time, this function makes the inverter trip () or issue an alarm (). With the communication
How to set the timer
By default, the communication
*Timer adjustment range
About 1 sec. (01H) to about 100 sec. (64H) / Timer off (0H)
How to specify what an inverter should do if a
By default, the communication
*Selection of
How to start the timer
If the timer is set from the operation panel, it will start automatically the instant when communication is established for the first time after the setting.
If the timer is set from the computer, it will start automatically the instant when communication is established after the setting.
If the timer setting is stored in the EEPROM, the timer will start when communication is established for the first time after the power has been turned on.
Note that, if the inverter number does not match or if a format error occurs, preventing the inverter from returning data, the timer function will assume that no communication has taken place and will not start.
How to disable the timer
To disable the timer, set its parameter to 0.
Ex.: To disable the timer function from the computer (To store the timer setting in the EEPROM)
Computer → Inverter | Inverter → Computer | |
(W08030)CR | (W08030000)CR | ... Sets the timer parameter to 0 to disable it. |
Timer
Time-out period
Computer link
PC → INV
Master INV
to Slave
INV
INV → PC
PC → INV
Master INV
to Slave
INV
The timer measures the time elapsed before the inverter ac- knowledges receipt of data after it acknowledged receipt of the previ- ous data.