. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements
Environmental Requirements
The array modules are designed to operate in the environment defined in Table
Table
Condition | Parameter | Requirement | |
| |||
E2400 10x and E2400 14x | |||
|
| ||
|
|
| |
| Operating Range | 10° C to 40° C (50° F to 104° F) | |
| Maximum Rate of Change | 10° C (18° F) per hour | |
Temperature | Storage Range | ||
Maximum Rate of Change | 15° C (27° F) per hour | ||
| |||
| Transit Range | ||
| Maximum Rate of Change | 20° C (36° F) per hour | |
| Operating Range | 20% to 80% | |
|
|
| |
| Storage Range | 10% to 90% | |
Relative Humidity |
|
| |
Transit Range | 5% to 95% | ||
No condensation | |||
|
| ||
| Maximum Dew Point | 26° C (79° F) | |
| Maximum Gradient | 10% per hour | |
|
|
| |
Sound | Sound Power | 6.0 bels | |
|
| ||
Sound Pressure | 60 dBA | ||
| |||
|
|
| |
Altitude | Operating and Storage | 3000 m (9840 ft.) | |
(Above Sea Level)1 |
|
| |
Transit | 12,000 m (40,000 ft.) | ||
|
|
| |
Altitude | Operating, Storage, | 30.5 m (100 ft.) | |
(Below Sea Level) | and Transit | ||
| |||
|
|
|
1 If you plan to operate an array module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level, lower the environmental temperature 1.7° C (3.3° F) for every 1000 m (3280 ft.) above sea level.
Table
Model | Low Profile (LP) | Half Height (HH) | |
18 GB and 36 GB Drives | 36 GB and 73 GB Drives | ||
| |||
|
|
| |
E2400 10x | 1187 Btu/hr (0.35 kVA or 347 W) | 1221 Btu/hr (0.37 kVA or 357 W) | |
|
|
| |
E2400 14x | 1118 Btu/hr (0.328 kVA or 327 W) | Not applicable. | |
|
|
|
Command Module and Drive Module Site Preparation Guide |