Func. |
| Default | Set | |
Name / Description | Value | |||
Code | Value | |||
| ||||
|
|
| ||
|
|
|
| |
|
|
|
| |
A146 | ADD direction select | 00 |
| |
| • 00 Plus (adds A145 value to output frequency) |
|
| |
| • 01 Minus (subtracts A145 value from output |
|
| |
| frequency) |
|
| |
|
|
|
| |
A151 | Pot. input active range start frequency | 0.0 |
| |
|
|
|
| |
A152 | Pot. input active range end frequency | 0.0 |
| |
|
|
|
| |
A153 | Pot. input active range start current | 0.0 |
| |
|
|
|
| |
A154 | Pot. input active range end current | 0.0 |
| |
|
|
|
| |
A155 | Pot. input start frequency enable | 01 |
| |
|
|
|
|
“B” Group: Fine-tuning Functions
Func. |
| Default | Set | |
Name / Description | Value | |||
Code | Value | |||
| ||||
|
|
| ||
|
|
|
| |
|
|
|
| |
B001 | Selection of automatic restart mode | 00 |
| |
| • 00 Alarm output after trip, automatic restart |
|
| |
| disabled |
|
| |
| • 01 Restart at 0Hz |
|
| |
| • 02 Resume operation after frequency |
|
| |
| matching |
|
| |
| • 03 Resume previous freq. after freq. matching, |
|
| |
| then decelerate to stop and display trip info |
|
| |
|
|
|
| |
B002 | Allowable | 1.0 |
| |
|
|
|
| |
B003 | Retry wait time before motor restart | 1.0 |
| |
|
|
|
| |
B004 | Instantaneous power failure / | 00 |
| |
| alarm enable |
|
| |
| • 00 Disable |
|
| |
| • 01 Enable |
|
| |
|
|
|
| |
B005 | Number of restarts on power failure / under- | 00 |
| |
| voltage trip event |
|
| |
| • 00 Restart 16 times |
|
| |
| • 01 Always restart |
|
| |
|
|
|
| |
B012/ | Level of electronic thermal setting | Rated |
| |
B212 |
| current of |
| |
|
| each inverter |
| |
|
|
|
| |
B013/ | Electronic thermal characteristic | 01 |
| |
B213 | • 00 Reduced torque1• 01 Const. torque |
|
| |
| • 02 Reduced torque2 |
|
| |
|
|
|
|
22