Hitachi series inverter manual Wire Connectors, Fuse and Circuit Breaker Sizes

Page 5

 

Wire Size

Torque Range

Terminal Connector

Range

 

 

 

(AWG)

ft-lbs

(N-m)

 

 

 

 

 

 

 

 

Logic/Analog connector

30—16

0.16—0.19

0.22—0.25

 

 

 

 

Relay connector

30—14

0.37—0.44

0.5—0.6

 

 

 

 

Wire Connectors

Warning: Field wiring connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by the con- nector manufacturer.

Terminal (ring lug)

Cable support

Cable

Fuse and Circuit Breaker Sizes

The inverter’s input power wiring must include UL Listed, dual-element, 600V fuses, or UL Listed, inverse-time, 600V circuit breakers.

200V Models

Motor output

Inverter Model

Ampere Rating for

 

 

kW

HP

 

Fuse or Breaker

 

 

 

 

 

 

 

 

 

 

0.2

1/4

–002NFE(F)2/NFU2

10

 

 

 

 

0.4

1/2

–004NFE(F)2/NFU2

10

 

 

 

 

0.55

3/4

–005NFE(F)2

10

 

 

 

 

0.75

1

–007NFE(F)2/NFU2

15

 

 

 

 

1.1

1 1/2

–011NFE(F)2

15

 

 

 

 

1.5

2

–015NFE(F)2/NFU2

20 (single ph.)

 

 

 

15 (three ph.)

 

 

 

 

2.2

3

–022NFE(F)2/NFU2

30 (single ph.)

 

 

 

20 (three ph.)

 

 

 

 

3.7

5

–037LFU2

30

 

 

 

 

5.5

7 1/2

–055LFU2

40

 

 

 

 

7.5

10

–075LFU2

50

 

 

 

 

3

Image 5
Contents L2002 Series Inverter Quick Reference Guide Page UL Cautions, Warnings, and Instructions Wiring Warnings for Electrical Practices and Wire SizesAWG Terminal Tightening Torque and Wire SizeFuse and Circuit Breaker Sizes Wire ConnectorsMotor Overload Protection L3 U/T1 V/T2 W/T3 Power Circuit TerminalsDescription Ratings and Notes Control Circuit TerminalsAL2 L200 Basic Wiring DiagramHitachi Inverter Keypad OperationPage Keypad Navigation Map Program ModeStep Description Via Keypad Via Logic Terminals Powerup TestBasic Error Codes Error CodesE60 Error Trip ConditionsRestoring Factory Default Settings Group Monitoring Functions Parameter TablesTrip History and Inverter Status Monitor ModeGroup Standard Functions Group Main Profile ParametersFunc Default Set Name / Description Value Code Characteristic curve selection AVR voltage select Group Fine-tuning Functions Overload restriction operation mode Group Intelligent Terminal Functions C082 OI input span calibration Func Default Set Name / Description Group Expansion Card Functions Group Motor Constants FunctionsIntelligent Input Terminal Listing Symbol Code Input Terminal NameIntelligent Output Terminal Listing Analog Input ConfigurationOption Function Name Description Corresponding Code Analog Output Function Listing