| Wire Size | Torque Range | |
Terminal Connector | Range |
|
|
| (AWG) | ||
|
|
|
|
|
|
|
|
Logic/Analog connector | |||
|
|
|
|
Relay connector | |||
|
|
|
|
Wire Connectors
Warning: Field wiring connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by the con- nector manufacturer.
Terminal (ring lug)
Cable support
Cable
Fuse and Circuit Breaker Sizes
The inverter’s input power wiring must include UL Listed,
200V Models
Motor output | Inverter Model | Ampere Rating for | |
|
| ||
kW | HP |
| Fuse or Breaker |
|
| ||
|
|
|
|
|
|
|
|
0.2 | 1/4 | 10 | |
|
|
|
|
0.4 | 1/2 | 10 | |
|
|
|
|
0.55 | 3/4 | 10 | |
|
|
|
|
0.75 | 1 | 15 | |
|
|
|
|
1.1 | 1 1/2 | 15 | |
|
|
|
|
1.5 | 2 | 20 (single ph.) | |
|
|
| 15 (three ph.) |
|
|
|
|
2.2 | 3 | 30 (single ph.) | |
|
|
| 20 (three ph.) |
|
|
|
|
3.7 | 5 | 30 | |
|
|
|
|
5.5 | 7 1/2 | 40 | |
|
|
|
|
7.5 | 10 | 50 | |
|
|
|
|
3