5.4 Wiring Method
Do not conduct wiring work when power is applied.
Wiring while power is applied can cause electric shock.
DON’T
Do not work on piping and wiring with wet hands.
Wet hands may result in electric shock.
DON’T
5.4.1Terminal Treatment of Cables
Proceed as follows to treat the terminals at the converter side of the flow rate signal and excitation cable and to connect these cables to the terminal block. Use appropriate cables referring to 5.1 "Installation Cables." Attach and crimp a round type M4 insulated crimping terminal to the end of each cable.
Excitation cable
Strip the sheath from the end of each wire as shown in Figure 5.2 and attach and crimp an M4 crimping terminal with insulated sleeve to the end of each wire and then connect the crimped terminals to X and Y of the terminal block. Connect the terminal of red wire to E of the terminal block.
M4 crimped terminal
XBlack
ERed
YWhite
25 to 45mm
Figure 5.2 Terminal Treatment of Excitation Cable