Totalizer operation using digital input signals
Totalizer and pulse output can be operated.
Remote operations of the totalizer and pulse output can be performed using the Digital Input signals.
Follow the procedure in 8.2.14 “Digital I/O Function” and set the Digital Input (DI) functions.
Operation using Digital Input signals (Standard product, Control signal level: High level)
Digital Input function DI input Totalizer, pulse output operation
Low level Stops Totalizer Start/Stop
High level Outputs
High level Clears (resets) the totalizer and stops Totalizer Reset/Start
Low level Outputs
It is possible to reverse the DI control signal levels by setting the digital input control signal levels.
When high level (1:H LEVEL) is selected: The operation with the signal level is the same as the
standard product shown in the above table.
When low level (0:L LEVEL) is selected: The operation with the signal level becomes as shown
below.
Operation using Digital Input signals (Control signal level: Low level)
Digital input function DI input Totalizer and pulse output operation
Low level Outputs Totalizer Start/stop
High level Stops
High level Outputs Totalizer Reset/Start
Low level Clears (resets) the totalizer and stops.