6F8A0917

Totalizer operation using digital input signals

Totalizer and pulse output can be operated.

Remote operations of the totalizer and pulse output can be performed using the Digital Input signals. Follow the procedure in 8.2.14 “Digital I/O Function” and set the Digital Input (DI) functions.

Operation using Digital Input signals (Standard product, Control signal level: High level)

Digital Input function

DI input

Totalizer, pulse output operation

 

 

 

Totalizer Start/Stop

Low level

Stops

 

 

 

 

High level

Outputs

 

 

 

Totalizer Reset/Start

High level

Clears (resets) the totalizer and stops

 

 

 

 

Low level

Outputs

 

 

 

It is possible to reverse the DI control signal levels by setting the digital input control signal levels.

When high level (1:H LEVEL) is selected: The operation with the signal level is the same as the standard product shown in the above table.

When low level (0:L LEVEL) is selected: The operation with the signal level becomes as shown below.

Operation using Digital Input signals (Control signal level: Low level)

Digital input function

DI input

Totalizer and pulse output operation

 

 

 

Totalizer Start/stop

Low level

Outputs

 

 

 

 

High level

Stops

 

 

 

Totalizer Reset/Start

High level

Outputs

 

 

 

 

Low level

Clears (resets) the totalizer and stops.

 

 

 

- 131 -

Page 132
Image 132
Toshiba L5232 manual Totalizer operation using digital input signals, 131