5.4.3Grounding

The external ground terminal of the detector and the FG terminal of the converter (or external ground terminal of the converter) must be grounded securely with Class D grounding (grounding resistance 100Ω or less). Use an IV wire 5.5mm2 or more for grounding wire.

In addition, do not share the grounding wire with other equipment where grounding current may flow. (An independent grounding is preferable.)

If it is difficult to carry out grounding work at the detector side due to a pit installation or other reasons, use a 3-core cable for the excitation cable and connect the E terminal of the detector to the E terminal or other reasons as shown in Figure 5.9(b), of the converter. (The E terminal of the converter is internally connected to the FG terminal and the converter housing.)

Converter

A

B

X

 

terminal block

G

E

Y

FG

External ground

 

 

 

 

terminal

 

 

 

 

Twisting shields

 

 

 

Class D grounding

 

 

 

 

 

 

 

 

(Ground resistance 100 or less)

Input signal cable

 

 

 

 

Twisting shields

 

 

 

Excitation cable

 

 

 

 

Ground terminal

 

 

G

 

E

 

A

B

X

Y

 

 

 

 

Class D ground

 

 

 

 

(Ground resistance 100 or less)

Detector terminal block

Figure 5.9(a) Wiring between Detector and Converter

- 27 -

Page 28
Image 28
Toshiba L5232 manual Grounding, 9a Wiring between Detector and Converter