8.2.11 Current Output Setting Used When an Alarm Occurs

The current output value setting used when an alarm occurs is the function to fix the current output to a pre-selected value if a fluid empty alarm or a self-diagnosis alarm occurs.

For the type of alarms to fix the current output, see the alarm output factor setting in 8.2.19 “Self-Diagnosis Function.”

Select the current output value used when an alarm occurs from the table shown below.

Current output setting function used when an alarm occurs

Selection

Current output value when an alarm occurs

 

 

1:UNDER 3.0mA

3.0mA or less

 

 

2:4.0mA

4.0mA

 

 

3:HOLD

Fixed to the current output

 

 

4:OVER 24.0mA

24.0mA or more

 

 

Checking the current output value used when an alarm occurs

Proceed as follows to check the current output value used when an alarm occurs.

Switch operation

Display example

Description

 

 

 

 

 

Select D3: 420 ALM. OUT from the setting item selection

 

D3: 4-20 ALM.OUT

menu.

 

2:4.0mA

The currently set current output value used when an alarm

 

 

occurs appears.

D3: 4-20 ALM.OUT

Returns to the menu of setting item selection.

- 83 -

Page 84
Image 84
Toshiba L5232 Current Output Setting Used When an Alarm Occurs, Current output setting function used when an alarm occurs