8.2.11 Current Output Setting Used When an Alarm Occurs
The current output value setting used when an alarm occurs is the function to fix the current output to a
For the type of alarms to fix the current output, see the alarm output factor setting in 8.2.19
Select the current output value used when an alarm occurs from the table shown below.
Current output setting function used when an alarm occurs
Selection | Current output value when an alarm occurs |
|
|
1:UNDER 3.0mA | 3.0mA or less |
|
|
2:4.0mA | 4.0mA |
|
|
3:HOLD | Fixed to the current output |
|
|
4:OVER 24.0mA | 24.0mA or more |
|
|
Checking the current output value used when an alarm occurs
Proceed as follows to check the current output value used when an alarm occurs.
Switch operation | Display example | Description |
|
|
|
|
| Select D3: 4−20 ALM. OUT from the setting item selection |
| D3: | menu. |
| 2:4.0mA | The currently set current output value used when an alarm |
|
| occurs appears. |
D3:
Returns to the menu of setting item selection.
- 83 -