13.2.2 Flow rate indication is not correct

START

Is the velocity range correctly set?

YES

Is zero point correctly set?

YES

NO

NO

Set it correctly according to 8. “Parameter Settings/Adjustment.”

Perform zero adjustment according to 6. “Operation” and 8.5 “Zero Adjustment.”

Is the exciting current correct?

YES

NO

Set the exciting current correctly according to 8. “Parameter Settings.”

Isn't the inside wall of detector pipe or electrode contaminated?

NO

Is the output load resistance 1k or less?

YES

Aren't there two load resistors connected to the output in parallel?

NO

Is accuracy calculated as follows?

(Measured flow rate) (Actual flow rate)

Actual flow rate

100 (%)

YES

Contact your nearest Toshiba representative.

YES

NO

YES

NO

Clean the inside wall of the detector pipe to remove the deposits.

Design the output circuit so that the output load resistance is less than 1 k.

Connect the two load resistors in series, if necessary.

Calculate as shown on the left.