6F8A0917
Digital Input Function
DI FUNCT. |
| Digital input function |
|
|
|
1: NO USE | Not used |
|
|
|
|
2: C STA/STP | Totalizer | Start/Stop control |
|
|
|
3: C RES/STA | Totalizer | Reset/Start control |
|
| |
4: RANGE SW1 | ||
|
| |
5: ZERO ADJ | Still water zero adjustment start | |
|
| |
6: FIXED OUT | ||
|
| |
7: RANGE SW2 | ||
|
|
|
Level setting for digital input control signal (for totalizer control only)
For totalizer control (items indicated byabove), the operating level (active level) for input control signal can be selected for each DI terminal.
DI DET LEVEL | Control signal level |
|
|
1: L LEVEL | Low level active |
|
|
2: H LEVEL | High level active |
|
|
The operation for control signal input is shown below depending on the active level setting.
Digital input function setting | Control signal | Operation when control signal is input | |
level setting | |||
|
| ||
|
|
| |
| L LEVEL | High signal: Totalization Stop | |
CNT STA/STP | Low signal: Totalization Start | ||
| |||
(Totalizer Start/Stop) |
|
| |
H LEVEL | High signal: Totalization Start | ||
| Low signal: Totalization Stop | ||
|
| ||
|
|
| |
| L LEVEL | High signal: Totalization Start | |
CNT RES/STA | Low signal: Totalization Reset | ||
| |||
(Totalizer Reset/Start) |
|
| |
H LEVEL | High signal: Totalization Reset | ||
| Low signal: Totalization Start | ||
|
| ||
|
|
|
- 90 -