6F8A0917
8.2.10 Low Cutoff value
The low cutoff is the fuction to forcefully fix the current output to 0% when the flow rate becomes equal or below the low cutoff value set near 0%.
The low cutoff value can be set from 0 to 10% and in increments of 0.1%. If 0% is set, the low cutoff function does not work.
Checking the low cutoff value
Proceed as follows to check the low cutoff value.
Switch operation | Display example | Description |
|
|
|
| D2: LOW CUT | Select D2: LOW CUT from the setting item selection menu. |
| 01.0 % | The currently set low cutoff value appears. |
D2: LOW CUT
Returns to the menu of setting item selection.
- 81 -