Changing the span value

The span value for each range is set.

The following is an example to show how to change the span value of Range 1 from 2.0m3/h to 100 l/min.

Switch operation

Display example

 

 

Description

 

 

 

 

 

 

 

C2: RANGE 1

Select C2: RANGE 1 from the setting item selection menu.

 

The currently set span value for Range 1 (2.0 m3/h in this

 

2.0000

m3/h

example) appears.

 

 

 

 

 

 

 

 

 

 

 

 

 

C2: RANGE 1

The cursor appears.

 

 

Press

further to move the cursor to the digit of volumetric

 

2.0000

m3/h

 

unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C2: RANGE 1

Change the volumetric unit to l.

 

Press

to move the cursor to the digit of time unit and

 

2000.0

l/h

 

likewise change the unit to min. (Note)

 

 

 

 

(The span value will be automatically changed as this unit is

 

33.333

l/min

 

changed.)

 

 

C2: RANGE 1

Move the cursor to the desired digit to change.

 

33.333

l/min

 

 

 

 

 

 

 

 

 

 

 

 

C2: RANGE 1

Change the number of the digit.

 

13.333

l/min

 

To change other digit, press

under this condition to move

 

 

 

 

the cursor to that digit and change the number there.

 

100.00

l/min

 

 

 

 

 

 

 

 

 

 

 

 

The display blinks and the set value is displayed for

 

C2: RANGE 1

confirmation.

 

 

Press

MENU/ENT

again to write the data. The cursor

 

100.00

l/min

 

disappears and returns to the condition that the set value is

 

 

 

 

 

 

displayed.

 

C2: RANGE 1

Returns to the menu of setting item selection.

Note: The items of unit are displayed cyclically as shown below:

Volumetric unit

 

 

 

 

 

Time unit

 

m3

l

 

ml

gal

bbl

/s

/min

qt

 

pt

ft

 

m

/d

/h

 

 

 

 

A combination of m/min, m/h , m/d, ft/min, ft/h and ft/d cannot be selected.