Changing the current output value used when an alarm occurs

The following is an example to show how to change the current output value, which is used when an alarm occurs, from 4.0mA (2: 4.0mA) to 24.0mA or more (4: OVER 24.0mA).

Switch operation

Display example

 

 

 

Description

 

 

 

 

 

 

 

 

 

Select D3: 420 ALM. OUT from the setting item selection

 

D3: 4-20

ALM.OUT

menu.

 

 

 

2:4.0mA

The currently set alarm output value used when an alarm

 

 

 

occurs appears.

 

 

 

 

 

 

 

 

D3: 4-20

ALM.OUT

The cursor appears.

 

2:4.0mA

 

 

 

 

 

 

 

 

 

 

 

 

 

D3: 4-20

ALM.OUT

Press

to select 4: OVER 24.0mA.

 

4:OVER 24.0mA

 

 

 

 

 

 

 

 

 

 

 

 

The display blinks and the set value is displayed for

 

D3: 4-20

ALM.OUT

confirmation.

 

Press

 

MENU/ENT

again to write the data. Then the cursor

 

4:OVER 24.0mA

 

 

disappears and the display returns to the condition that the

 

 

 

 

 

 

setting value is displayed.

D3: 4-20 ALM.OUT

Returns to the menu of setting item selection.

- 84 -

Page 85
Image 85
Toshiba L5232 manual Changing the current output value used when an alarm occurs