6F8A0917

Changing each setting for digital I/O

The following is an example to show how to change the function of Digital Output 1 from High limit alarm output (2:HIGH ALM) to Fluid empty alarm (A:EMPTY ALM).

To change other setting values, select the following function numbers.

Digital Output 1

 

F1: DO1 FNCTN

Digital Output 2

 

F2: DO2 FNCTN

Digital Output 3

 

F3: DO3 FNCTN

Digital Output 4

 

F4: DO4 FNCTN

Digital Output alarm status 1

 

F5: DO1 ALM STS

Digital Output alarm status 2

 

F6: DO2 ALM STS

Digital Output alarm status 3

 

F7: DO3 ALM STS

Digital Output alarm status 4

 

F8: DO4 ALM STS

Digital Input 1

 

 

G1: DI1 FNCTN

Digital Input 2

 

 

G2: DI2 FNCTN

Digital Input control signal level 1

 

G3: DI1 DET LEV

Digital Input control signal level 2

 

G4: DI2 DET LEV

 

 

 

 

 

Switch operation

Display example

 

 

Description

 

 

 

 

 

 

F1: DO1 FNCTN

Select F1: DO1 FNCTN from the setting item selection menu.

 

1:HIGH ALM

The currently set function of Digital Output 1 appears.

 

 

 

 

 

 

F1: DO1 FNCTN

The cursor appears.

 

1:HIGH ALM

 

 

 

 

 

 

 

 

 

 

F1: DO1 FNCTN

Select the output function A:EMPTY ALM.

 

A:EMPTY ALM

 

 

 

 

 

 

 

 

 

The display blinks and the set value is displayed for

 

F1: DO1 FNCTN

confirmation.

 

Press

MENU/ENT

again to write the data. Then the cursor

 

A:EMPTY ALM

 

disappears and the display returns to the condition that the

 

 

 

 

setting value is displayed.

F1: DO1 FNCTN

Returns to the menu of setting item selection.

- 92 -

Page 93
Image 93
Toshiba L5232 manual Changing each setting for digital I/O, Digital Output alarm status