Changing the meter size of the detector

The following is an example to change the meter size from 50mm to 10mm.

Switch operation

Display example

Description

 

 

 

 

A2: METER SIZE

Select A2: METER SIZE from the setting item selection.

 

50 mm

The currently set meter size (50mm in this example) appears.

A2: METER SIZE

The cursor appears.

 

50

mm

 

 

 

 

 

 

 

 

 

 

 

A2: METER SIZE

Change the set value for meter size to 100mm.

 

The set value for meter size can be changed using

switch.

100

mm

(Note 1)

 

 

 

 

 

 

 

 

 

 

The display blinks and the set value is displayed for

 

A2: METER SIZE

confirmation.

 

Press

MENU/ENT

again to write the data. Then the cursor

100 mm

disappears and the display returns to the condition that the

 

 

 

 

setting value is displayed.

 

A2: METER SIZE

Returns to the menu of setting item selection.

Note 1: The meter size is displayed cyclically as shown below:

In the case of the converter for large meter size detector (LF232*B)

2.5mm 600mm

700mm 3000mm

0.1inch 24inch

28inch 120inch

* For partially filled pipes detectors (LF232*F) : 624inch (150600mm )

Note 2: If the setting value for meter value is changed, the setting value by flow unit and the setting value for exciting frequency of no concern may be rewritten.

After the meter size is set, be sure to check the setting values of Range, Count (Pulse) Rate and Exciting Frequency.