6F8A0917

11. Communications Function

The LF232 Series Converters are equipped with HART*1 protocol to transmit digital signals over the 4 to 20mA output line. The AF900 hand-held terminal (hereafter called HHT) can be used to check or change various parameters, calibrate the flowmeter or monitor the measured value from a remote place.

For the detailed operation and specification of HHT, refer to the "Hand-held Terminal for Sensor with Communication Function AF900 Instruction Manual" (6F8A0849).

*1 HART protocol: The “HART protocol”, which stands for Highway Addressable Remote Transducer, is the name of the communication protocol for industry sensors that is recommended by HCF (HART Communication Foundation).

11.1Connection with the HHT terminal

Connect the probe cable of the HHT terminal in parallel with the load resistor which is wired from the current output terminals (+ and ) of the flowmeter. Since the tip end of the probe cable is a pair of clips, use a junction terminal or a terminal block, etc. to connect with the clips of the probe. To connect the HHT directly to the flowmeter, use the terminals + and of the converter main unit terminal block. Though the current output terminal has polarity, the HHT connection cable has no polarity.

See Figure 11.1 and 11.2 for connection examples.

4 to 20 mADC (Communication line)

Load resistor

Terminal block or junction terminal

LF232 Converter

HHT

Figure 11.1 Connections to the Current Output Line

- 149 -

Page 150
Image 150