11. Communications Function
The LF232 Series Converters are equipped with HART*1 protocol to transmit digital signals over the 4 to 20mA output line. The AF900
For the detailed operation and specification of HHT, refer to the
*1 HART protocol: The “HART protocol”, which stands for Highway Addressable Remote Transducer, is the name of the communication protocol for industry sensors that is recommended by HCF (HART Communication Foundation).
11.1Connection with the HHT terminal
Connect the probe cable of the HHT terminal in parallel with the load resistor which is wired from the current output terminals (+ and −) of the flowmeter. Since the tip end of the probe cable is a pair of clips, use a junction terminal or a terminal block, etc. to connect with the clips of the probe. To connect the HHT directly to the flowmeter, use the terminals + and − of the converter main unit terminal block. Though the current output terminal has polarity, the HHT connection cable has no polarity.
See Figure 11.1 and 11.2 for connection examples.
4 to 20 mADC (Communication line)
Load resistor
Terminal block or junction terminal
LF232 Converter
HHT