15. Specifications

15.1 Specifications

Detector Combined Specifications
1. Measuring range: (measuring range in terms of flow velocity)
0 –1.0 ft/s to 0 – 32.8 ft/s (0 – 0.3 m/s to 0 –10 m/s)
For partially filled pipes detectors (Combined detector is LF502)
Meter Measurement range
6” (150mm) 0 – 264 GPM(std) to 0 – 1320 GPM
(0 – 60 m3/h to 0 – 300 m3/h )
8” (200mm ) 0 – 484 GPM(std) to 0 – 2420 GPM
(0 – 110 m3/h to 0 – 550 m3/h )
10” (250mm ) 0 – 770 GPM(std) to 0 – 3850 GPM
(0 – 175 m3/h to 0 – 875 m3/h )
12” (300mm ) 0 – 1100 GPM(std) to 0 – 5500 GPM
(0 – 250 m3/h to 0 1250 m3/h )
14” (350mm ) 0 – 1540 GPM(std) to 0 – 7700 GPM
(0 – 350 m3/h to 0 1750 m3/h )
16” (400mm ) 0 – 1980 GPM(std) to 0 – 9900 GPM
(0 – 450 m3/h to 0 2250 m3/h )
20” (500mm ) 0 – 3124 GPM(std) to 0 – 15620 GPM
(0 – 710 m3/h to 0 3550 m3/h )
24” (600mm ) 0 – 4400 GPM(std) to 0 – 22000 GPM
(0 – 1000 m3/h to 0 – 5000 m3/h )
(Above flow rate is almost 0 – 3.28 ft/s (std) to 0 – 16.4 ft/s (0 – 1 m/s to 0 – 5 m/s ) flow velocity.)