400V Models
Motor output | Inverter Model | Ampere Rating for | |
|
| ||
kW | HP |
| Fuse or Breaker |
|
| ||
|
|
|
|
|
|
|
|
0.4 | 1/2 | 3 | |
|
|
|
|
0.75 | 1 | 6 | |
|
|
|
|
1.5 | 2 | 10 | |
|
|
|
|
2.2 | 3 | 10 | |
|
|
|
|
3.0 | 4 | 15 | |
|
|
|
|
4.0 | 5 | 15 | |
|
|
|
|
5.5 | 7 1/2 | 20 | |
|
|
|
|
7.5 | 10 | 25 | |
|
|
|
|
Motor Overload Protection
Hitachi L2002 inverters provide solid state motor overload protection, which depends on the proper setting of the following parameters:
•B012 “electronic overload protection”
•B212 “electronic overload protection, 2nd motor”
Set the rated current [Amperes] of the motor(s) with the above parame- ters. The setting range is 0.2 * rated current to 1.2 * rated current.
Warning: When two or more motors are connected to the inverter, they cannot be protected by the electronic overload pro- tection. Install an external thermal relay on each motor.
4