Terminal | Description | Ratings and Notes | |
Name | |||
|
| ||
|
|
| |
|
|
| |
L (right) | GND for logic inputs | Sum of input 1 to 5 currents | |
|
| (Note: Do not ground) | |
|
|
| |
11, 12 | Discrete logic outputs | 50 mA max. ON current, | |
|
| 27 VDC max. OFF voltage | |
|
|
| |
CM2 | GND for logic outputs | 100 mA max for sum of | |
|
| terminals 11 and 12 currents | |
|
|
| |
AM | Analog voltage output | 0 to 10VDC, 1 mA max., 50% | |
|
| duty cycle | |
|
|
| |
L (left) | GND for analog signals | Sum of OI, O, H, and AM | |
|
| currents (return) | |
|
|
| |
OI | Analog input, current | 4 to 19.6 mA range, 20 mA | |
|
| nominal | |
|
|
| |
O | Analog input, voltage | 0 to 9.6 VDC range, 10VDC | |
|
| nominal, 12VDC max., input | |
|
| impedance 10 kΩ | |
|
|
| |
H | +10V analog reference | 10VDC nominal, 10 mA max. | |
|
|
| |
AL0 | Relay common contact | Contact rating | |
|
| Max resistive load = 250VAC, | |
AL1 | Relay contact, normally | 2.5A; 30VDC 3A; | |
| closed during RUN | Max inductive load = 250VAC, | |
|
| 0.2A; 30VDC 0.7A | |
AL2 | Relay contact, normally | Minimum load = 5VDC 100mA, | |
| open during RUN | 100VAC 10mA | |
|
|
|
7