GE Motor Protection System, LM10 Attribute, Access, Name/Description, Data Type, Value

Page 62

DEVICENET OPERATIONS

 

CHAPTER 5: COMMUNICATIONS

 

 

 

 

 

 

 

Attribute

Access

Name/Description

Data Type

Value

 

 

 

 

 

 

 

0x09

Get/set

User setting, Run 2, stall

F4

Trip, Time

 

 

 

 

 

 

 

0x0A

Get/set

User setting, Run 1, unbalance

F5

Trip, Time

 

 

 

 

 

 

 

0x0B

Get/set

User setting, Run 2, unbalance

F5

Trip, Time

 

 

 

 

 

 

 

0x0C

Get/set

User setting, Run 1, load loss

F6

Trip, Time

 

 

 

 

 

 

 

0x0D

Get/set

User setting, Run 2, load loss

F6

Trip, Time

 

 

 

 

 

 

 

0x0E

Get/set

User setting, power transformers

F7

0 to 11

 

 

 

 

 

 

 

0x0F

Get/set

User setting, current transformers

F8

1 to 15

 

 

 

 

 

 

 

0x10

Get/set

User setting, auxiliary sense 1 timer

F9

0.1 (0 to 250)

 

 

 

 

 

 

 

0x11

Get/set

User setting, auxiliary sense 2 timer

F10

0.1 (0 to 250)

 

 

 

 

 

 

 

0x12

Get/set

User setting, auxiliary relay flags

F11

16 bits

 

 

 

 

 

 

 

0x15

Get

Motor run time hours

UINT

Hours

 

 

 

 

 

 

 

0x1A

Get/set

Configure passcode

UINT

Code (0)

 

 

 

 

 

 

 

0x24

Get/set

User setting, motor type

F12

Type 0 to 5

 

 

 

 

 

 

 

0x25

Get/set

User setting, loops through CT

F13

1 to 4

 

 

 

 

 

 

 

0x26

Get/set

Flags (Mrun, AutoRestart, O/V Volt

F14

16 bits

 

 

 

Enable, DNFault, 50 Hz)

 

 

 

 

 

 

 

 

 

0x2E

Call

Reset LM10*

N/A

---

 

0x1C

Call

Reset factory default user settings

N/A

---

 

 

 

 

 

 

 

0x2F

Get

Trip class

F17

---

 

 

 

 

 

 

 

0x30

Get

MAC ID

F18

---

 

 

 

 

 

 

 

0x31

Get

DeviceNet baud rate

F19

---

 

 

 

 

 

 

 

0x34

Get

Input switch status

F25

16 bits

 

 

 

 

 

 

 

0x38

Get

Remaining cool-down period

F26

16 bits

 

 

 

 

 

 

 

0x39

Get/set

Poll data group

F15

1 to 4

 

 

 

 

 

 

 

0x3A

Get/set

Run1-Run2 time delay

F16

0 to 600 sec.

 

 

 

 

 

 

 

0x3B

Get/set

Run2-Run1 time delay2

F16

0 to 600 sec.

 

0x40

History

Status (send data byte 0 for current, 1

F24

---

 

 

 

to 10 for history)

 

 

 

 

 

 

 

 

 

0x41

History

Phase A current

F23

0.1 A

 

 

 

 

 

 

 

0x42

History

Phase B current

F23

0.1 A

 

 

 

 

 

 

 

0x43

History

Phase C current

F23

0.1 A

 

 

 

 

 

 

 

0x44

History

Ground current

F23

0.1 A

 

 

 

 

 

 

 

0x45

History

Voltage

UINT

volts

 

 

 

 

 

 

 

0x46

History

Power factor

UINT

percent

 

 

 

 

 

 

 

0x47

History

Watts

F23

0.1 kW

 

 

 

 

 

 

 

0x48

History

Operating current

F23

0.1 A

 

 

 

 

 

 

 

0x49

History

Current unbalance

UINT

percent

 

 

 

 

 

 

 

0x50

Login

User

---

---

 

 

 

 

 

 

 

0x51

Login

Configuration

UINT

Passcode

 

 

 

 

 

 

 

0x52

Login

Calibration

UINT

Passcode

 

 

 

 

 

 

*This call function has the same result as pressing the Reset key on the PDU display Applies to revisions 1.50 and higher

The data type format codes for class code 0x64, instance 1 are shown below.

5–56

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Image 62
Contents Multilin LM10 Motor Protection System Instruction ManualGE Consumer & Industrial 1601-0165-A62008 GE Multilin Incorporated. All rights reserved 1 INTRODUCTION Table of Contents2 INSTALLATION 3 INTERFACE6 MISCELLANEOUS 4 FUNCTIONALITY5 COMMUNICATIONS APPENDIXINDEX A-171-IV 1.1.1 The LM10 Relay LM10 Motor Protection System Chapter 1 Introduction1.1 Description 1.2.2 Current and Voltage Inputs 1.2.1 Features1.2 Overview 1.2.3 Relay OutputsFIGURE 1-1 Functional Block Diagram 1.2.4 Power Supply1.2.5 Block Diagram 1.3.3 Switches 1.3 Features1.3.2 LED Indicators 1.3.1 Programming and Display UnitFIGURE 1-2 LM10 Features Changes to switch settings will not take effect until power is cycledDIP Switch Position Baud RateTable 1-1 LM10 Order Codes 1.4 Ordering1.4.1 Order Codes LM10PHASE CURRENT SpecificationsGROUND FAULT 1.5.1 Protection ElementsPOWER SUPPLY POWERPOWER FACTOR 1.5.3 Control Functions0 to 120 CONTACT INPUTStop, Reset, DeviceNet control 200 toThermal overload CT 1.5.5 CT DimensionsGround fault CT 1.5.6 OutputsSERIAL COMMUNICATIONS EnvironmentalApprovals/Certification 1.5.81-12 2.1.1 DeviceNet LM10 Motor Protection System Chapter 2 Installation2.1 Wiring 2.1.2 RS232 Port2.1.3 Control Terminals Table 2-1 Control Connections2.1.5 Wiring Diagram 2.1.4 Sensor Pack InputFIGURE 2-4 LM10 Wiring Diagram CHAPTER 2 INSTALLATION2.2 Mounting 2.2.1 LM10 MountingFIGURE 2-7 PDU Door-mount Dimensions 2.2.2 PDU Door MountFIGURE 2-6 LM10 Backplate Dimensions 3.1.1 Liquid Crystal Display LM10 Motor Protection System Chapter 3 Interface3.1 PDU Operations 3.1.2 LEDspower factor, kW, average current, and current unbalance. Pressing the History button again advances to the next history record 3.2.1 Main Startup Screen 3.2.3 Configuration Menu3.2 PDU Screens and Menus 3.2.2 History Record and Status ScreensRun 2 to Run 1 delay between forward and reverse or between speeds 3.3.2 Functional Details 3.3 EnerVista LM10 Software3.3.1 Description Table 3-1 EnerVista Hot Keys 4.1.1 Descriptions 4.1 Overcurrent Fault ConditionsLM10 Motor Protection System Chapter 4 Functionality FIGURE 4-1 Cold Motor Trip Curves FIGURE 4-2 Hot Motor Trip Curves CHAPTER 4 FUNCTIONALITYFIGURE 4-4 Cool Down Times 4.1.2 Trip Curves ExampleFIGURE 4-3 Trip Curve with Jam and Stall Enabled Page Table 4-1 LM10 Programmable Parameters 4.2 Configuration Settings4.2.1 Overview 4-30 4.2.2 Main MenuCONFIGURATION SETTINGSCHAPTER 4 FUNCTIONALITY 4.2.3 Language PATH Configuration Ø ENGLISH/SPANISHPATH Configuration ØØ CTs & CPTs 4.2.4 CTs and CPTsPATH Configuration ØØØØ Run 1 Setup 4.2.6 Run 1 and Run 2 SetupPATH Configuration ØØØ Starter Type 4.2.5 Starter TypeΔ = phase current - average current PATH Configuration ØØØØØØ Other Settings 4.2.8 Other SettingsPATH Configuration ØØØØØ Time Delays 4.2.7 Time DelaysMaintained off DevNet Fault onReset Run Hrs Auto Restart off4.2.9 Auxiliary Relay Faults PATH Configuration ØØØØØØØ Aux Relay Faults4.2.10 Passcode and Login PATH Configuration ØØØØØØØØ Aux Relay FaultsPATH Configuration ØØØØØØØØØØ Factory Default 4.2.12 Factory DefaultPATH Configuration ØØØØØØØØØ Run Operations 4.2.11 Run OperationsRun, Fault 4.3 Status Values4.3.1 Main Menu RangeThis value can be reset via the Reset Run Hrs configuration setting Range Overcurrent, Gr. Fault, Jam, Stall CuUnbalance, LdLoss, DevNet 4.4 History Values4.4.1 Last Trip Data Fault, Dev Stop, Voltage, Aux Sense Range 0.0 to 3200.0 AMotor Status Running AUX Sense 1 Fault4.5 Motor Start/Stop Logic Motor StopRUN1 Switch Input Motor RUN CommandsMotor STOP Commands RUN1 PDU Command4-44 5.1.1 Description LM10 Motor Protection System Chapter 5 Communications5.1 DeviceNet Operations 5.1.2 Poll DataTable 5-3 Poll Data Group Table 5-1 Poll Data GroupTable 5-2 Poll Data Group Table 5-4 Poll Data Group5.1.5 DeviceNet Object 5.1.3 Identity object5.1.4 Message Router UINT = 16 bit unsigned integerDevice outputs see format and mapping below 5.1.6 Assembly ObjectBaud Rate, value 0 to 2 125, 250, and 500 kbps Assembly Object, Class Code 4, Instance CHAPTER 5 COMMUNICATIONS Data Formats for Device Inputssee below Assembly Object, Class Code 4, Instance Connection Object, Class Code 5, Attributes 5.1.7 Connection ObjectConnection Object, Class Code 5, Services Connection Object, Class Code 5, Instance 2 polled input/output connection USINT = 8-bit unsigned integer UINT = 16-bit unsigned integer 5.1.8 ACK Handler Object5.1.9 Overload Object 5.1.10 Extension Object UINT = 16-bit unsigned integerName/Description 5.1.11 Data Formats F2 Ground FaultF7 Power Transformer F1 Full Load Current 16-bit unsigned integerF10 Auxiliary Sense 2 / Run2-Run1 Time Delays F11 Auxiliary Relay Faults 16-bit bitmaskF9 Auxiliary Sense 1 / Run1-Run2 Time Delays F12 Starter TypeF16 Run1-Run2 and Run2-Run1 Time Delay 16-bit unsigned integer F14 Other Settings 16-bit BitmaskF15 Poll Data Group enumeration 16-bit unsigned integer F17 Trip ClassF23 16-bit Unsigned Integer F21 Motor Status 8-bit BitmaskF22 Motor Status 16-bit bitmask F24 Status Word 16-bit bitmaskF25 Input Switch Status 16-bit value use only lower byte 5.1.12 Special ApplicationSent by scanner CANID, MACID, 0x0E, 0x64, 0x01 5.2 Serial Port 5.2.1 Description5-64 6.1.1 Release Dates LM10 Motor Protection System Chapter 6 MiscellaneousRevision History 6.1.2 Changes to the ManualAdd Assembly Object, Class Code 4, Instance 105 Poll Data Group Table 6-4 Changes to Manual Since Release A3Change to Assembly Object, Class Code 4, Instance 101, Attribute Changes to Connection Object, Class Code 5, Instance 2 polled6.2 Warranty 6.2.1 GE Multilin WarrantyCHAPTER 6 MISCELLANEOUS WARRANTY6-68 A.1.1 Description LM10 Motor Protection System Appendix AA.1 DeviceNet Overview A.1.2 Controller Area Network CAN A.1.3 DeviceNet OperationsA.1.5 Pre-defined Master/Slave Connection Set A.1.6 DeviceNet FeaturesA.1.4 Explicit Messaging and Input/Output I/O Messaging A.1.7 Maximum Cable Lengths for DeviceNetTable A-2 Drop Cable Length Specification A.1.8 DeviceNet Specification HighlightsTable A-1 Trunk Cable Length Specification DescriptionThe Object Model Device ProfilesA.2 LM10 and GE Fanuc 90-30 with DeviceNet A.2.3 Network ConfigurationA.2.4 Configuration Procedure A.2.1 OverviewZ Also, set the Scan Interval and Reconnect Time A.2.5 Polling Input/Output ConnectionZ Select GE LM10 under GE Multilin Page Phase A values are displayed in %I00105 223 ⋅ 0.1 amps A.2.6 COS Change of State Input/Output Connection A.2.7 Cyclic Input/Output ConnectionA.2.8 Explicit Messaging Monitoring DataRung 3 has a Block Move word, 3 blocks Login Configuration Level to the LM10 FIGURE A-1 Ladder Logic for Data MonitoringMaking Setting Changes FIGURE A-2 Ladder Logic for Login ConfigurationLogin User Level to the LM10 FIGURE A-3 Ladder Logic for Setting ChangesFIGURE A-4 Ladder Logic for Login User A.3 LM10 and Allen-Bradley SLC500 via DeviceNet A.3.2 System SetupA.3.4 Setting Up the DeviceNet Network A.3.1 DescriptionA.3.5 Changing the Mode of Operation A.3.6 Configuring the Slave Device A.3.7 Control and Monitoring of the LM10 A.3.8 Explicit Messaging with the LM10 Relay Table A-4 Data Table Layout Table A-3 Status Codes Provided by ODVA SpecificationA.3.9 Data Table Layout Table A-6 Data for Explicit Message Response, M1 Transferred to N20 A.3.10 Ladder LogicTable A-5 Data to Get Trip Class Instance, and Attribute Table A-7 Data to Get Motor Run TimeTable A-8 Data for Explicit Message Response, M1 Transferred to N20 FIGURE A-9 Ladder Logic, Rungs 0000 to A-25FIGURE A-10 Ladder Logic, Rungs 0006 to A-26FIGURE A-11 Ladder Logic, Rungs 0009 to A-27A-28 Index Page LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL INDEX LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL