GE LM10, Motor Protection System A.2.8 Explicit Messaging, Monitoring Data, Description

Page 85

CHAPTER A:

LM10 AND GE FANUC 90-30 WITH DEVICENET™

ZDouble-click the added slave device to view the data area for Connection 2.

ZOpen the Reference View Table and add address %I00089.

ZTo interpret the 1 byte of status information for address %I00097, refer to Object Class 4, Instance 54 in Assembly Object on page 5– 48.

A.2.8 Explicit Messaging

Description:

Explicit messaging provides multi-purpose, point-to-point communication paths between two devices. It typically provides request/response-oriented network communication used to perform node configuration and problem diagnosis.

In the GE Multilin LM10 Motor Protection System. explicit messaging is used for configuration and monitoring.

Use the following procedure to set the network for explicit messaging:

ZFor the master side: In the Network Setting > DN9030 Master Properties menu, disable connections 1 and 2 by selecting Enable Explicit Connection.

ZSet the Message Request Size and Message Response Size to 20 bytes.

ZFor the slave side: In the Network Setting > Disable Connection 1 & 2 window, select Explicit Message Size set the value as 20 bytes.

ZConnect the PLC and download the hardware logic. The configuration should be shown as = EQ.

ZObserve the DeviceNet master module LEDs.

All three LEDs for NET POWER, MOD STATUS, and NET STATUS should turn solid green. Refer to LEDs on page 3–19to interpret the device LED status.

Explicit messaging between the DeviceNet master module and LM10 slave takes place using COMMREQ ladder instructions.

A communication request begins when a COMMREQ ladder instruction is activated in the PLC application program. The CPU sends the COMMREQ to the DeviceNet™ master module in the PLC system. The module receives the command and performs the requested function.

Monitoring Data:

The ladder logic for monitoring data from the GE LM10 Motor Protection System using COMMREQ is shown in Ladder Logic for Data Monitoring on page A–13.The ladder logic is configured as follows:

Rung 1 and 2 have a timer (thousands), as well as set and reset coils, which toggle the T1 contact after the timer PV value overflows. With the values shown, the T1 contact will toggle every five (5) seconds.

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

A–11

Image 85
Contents GE Consumer & Industrial LM10 Motor Protection System Instruction ManualMultilin 1601-0165-A62008 GE Multilin Incorporated. All rights reserved 2 INSTALLATION Table of Contents1 INTRODUCTION 3 INTERFACE5 COMMUNICATIONS 4 FUNCTIONALITY6 MISCELLANEOUS APPENDIXA-17 INDEX1-IV 1.1 Description LM10 Motor Protection System Chapter 1 Introduction1.1.1 The LM10 Relay 1.2 Overview 1.2.1 Features1.2.2 Current and Voltage Inputs 1.2.3 Relay Outputs1.2.5 Block Diagram 1.2.4 Power SupplyFIGURE 1-1 Functional Block Diagram 1.3.2 LED Indicators 1.3 Features1.3.3 Switches 1.3.1 Programming and Display UnitDIP Switch Position Changes to switch settings will not take effect until power is cycledFIGURE 1-2 LM10 Features Baud Rate1.4.1 Order Codes 1.4 OrderingTable 1-1 LM10 Order Codes LM10GROUND FAULT SpecificationsPHASE CURRENT 1.5.1 Protection ElementsPOWER FACTOR POWERPOWER SUPPLY 1.5.3 Control FunctionsStop, Reset, DeviceNet control CONTACT INPUT0 to 120 200 toGround fault CT 1.5.5 CT DimensionsThermal overload CT 1.5.6 OutputsApprovals/Certification EnvironmentalSERIAL COMMUNICATIONS 1.5.81-12 2.1 Wiring LM10 Motor Protection System Chapter 2 Installation2.1.1 DeviceNet 2.1.2 RS232 PortTable 2-1 Control Connections 2.1.3 Control Terminals2.1.4 Sensor Pack Input 2.1.5 Wiring DiagramCHAPTER 2 INSTALLATION FIGURE 2-4 LM10 Wiring Diagram2.2.1 LM10 Mounting 2.2 MountingFIGURE 2-6 LM10 Backplate Dimensions 2.2.2 PDU Door MountFIGURE 2-7 PDU Door-mount Dimensions 3.1 PDU Operations LM10 Motor Protection System Chapter 3 Interface3.1.1 Liquid Crystal Display 3.1.2 LEDspower factor, kW, average current, and current unbalance. Pressing the History button again advances to the next history record 3.2 PDU Screens and Menus 3.2.3 Configuration Menu3.2.1 Main Startup Screen 3.2.2 History Record and Status ScreensRun 2 to Run 1 delay between forward and reverse or between speeds 3.3.1 Description 3.3 EnerVista LM10 Software3.3.2 Functional Details Table 3-1 EnerVista Hot Keys LM10 Motor Protection System Chapter 4 Functionality 4.1 Overcurrent Fault Conditions4.1.1 Descriptions CHAPTER 4 FUNCTIONALITY FIGURE 4-1 Cold Motor Trip Curves FIGURE 4-2 Hot Motor Trip CurvesFIGURE 4-3 Trip Curve with Jam and Stall Enabled 4.1.2 Trip Curves ExampleFIGURE 4-4 Cool Down Times Page 4.2.1 Overview 4.2 Configuration SettingsTable 4-1 LM10 Programmable Parameters CONFIGURATION SETTINGSCHAPTER 4 FUNCTIONALITY 4.2.2 Main Menu4-30 PATH Configuration ØØ CTs & CPTs PATH Configuration Ø ENGLISH/SPANISH4.2.3 Language 4.2.4 CTs and CPTsPATH Configuration ØØØ Starter Type 4.2.6 Run 1 and Run 2 SetupPATH Configuration ØØØØ Run 1 Setup 4.2.5 Starter TypeΔ = phase current - average current PATH Configuration ØØØØØ Time Delays 4.2.8 Other SettingsPATH Configuration ØØØØØØ Other Settings 4.2.7 Time DelaysReset Run Hrs DevNet Fault onMaintained off Auto Restart offPATH Configuration ØØØØØØØ Aux Relay Faults 4.2.9 Auxiliary Relay FaultsPATH Configuration ØØØØØØØØ Aux Relay Faults 4.2.10 Passcode and LoginPATH Configuration ØØØØØØØØØ Run Operations 4.2.12 Factory DefaultPATH Configuration ØØØØØØØØØØ Factory Default 4.2.11 Run Operations4.3.1 Main Menu 4.3 Status ValuesRun, Fault RangeThis value can be reset via the Reset Run Hrs configuration setting 4.4.1 Last Trip Data 4.4 History ValuesRange Overcurrent, Gr. Fault, Jam, Stall CuUnbalance, LdLoss, DevNet Fault, Dev Stop, Voltage, Aux Sense Range 0.0 to 3200.0 A4.5 Motor Start/Stop Logic AUX Sense 1 FaultMotor Status Running Motor StopMotor STOP Commands Motor RUN CommandsRUN1 Switch Input RUN1 PDU Command4-44 5.1 DeviceNet Operations LM10 Motor Protection System Chapter 5 Communications5.1.1 Description 5.1.2 Poll DataTable 5-2 Poll Data Group Table 5-1 Poll Data GroupTable 5-3 Poll Data Group Table 5-4 Poll Data Group5.1.4 Message Router 5.1.3 Identity object5.1.5 DeviceNet Object UINT = 16 bit unsigned integerBaud Rate, value 0 to 2 125, 250, and 500 kbps 5.1.6 Assembly ObjectDevice outputs see format and mapping below Assembly Object, Class Code 4, Instance see below Data Formats for Device InputsCHAPTER 5 COMMUNICATIONS Assembly Object, Class Code 4, Instance Connection Object, Class Code 5, Services 5.1.7 Connection ObjectConnection Object, Class Code 5, Attributes Connection Object, Class Code 5, Instance 2 polled input/output connection 5.1.9 Overload Object 5.1.8 ACK Handler ObjectUSINT = 8-bit unsigned integer UINT = 16-bit unsigned integer UINT = 16-bit unsigned integer 5.1.10 Extension ObjectAttribute F7 Power Transformer F2 Ground Fault5.1.11 Data Formats F1 Full Load Current 16-bit unsigned integerF9 Auxiliary Sense 1 / Run1-Run2 Time Delays F11 Auxiliary Relay Faults 16-bit bitmaskF10 Auxiliary Sense 2 / Run2-Run1 Time Delays F12 Starter TypeF15 Poll Data Group enumeration 16-bit unsigned integer F14 Other Settings 16-bit BitmaskF16 Run1-Run2 and Run2-Run1 Time Delay 16-bit unsigned integer F17 Trip ClassF22 Motor Status 16-bit bitmask F21 Motor Status 8-bit BitmaskF23 16-bit Unsigned Integer F24 Status Word 16-bit bitmask5.1.12 Special Application F25 Input Switch Status 16-bit value use only lower byteSent by scanner CANID, MACID, 0x0E, 0x64, 0x01 5.2.1 Description 5.2 Serial Port5-64 Revision History LM10 Motor Protection System Chapter 6 Miscellaneous6.1.1 Release Dates 6.1.2 Changes to the ManualChange to Assembly Object, Class Code 4, Instance 101, Attribute Table 6-4 Changes to Manual Since Release A3Add Assembly Object, Class Code 4, Instance 105 Poll Data Group Changes to Connection Object, Class Code 5, Instance 2 polled6.2.1 GE Multilin Warranty 6.2 Warranty6-68 WARRANTYCHAPTER 6 MISCELLANEOUS A.1 DeviceNet Overview LM10 Motor Protection System Appendix AA.1.1 Description A.1.3 DeviceNet Operations A.1.2 Controller Area Network CANA.1.4 Explicit Messaging and Input/Output I/O Messaging A.1.6 DeviceNet FeaturesA.1.5 Pre-defined Master/Slave Connection Set A.1.7 Maximum Cable Lengths for DeviceNetTable A-1 Trunk Cable Length Specification A.1.8 DeviceNet Specification HighlightsTable A-2 Drop Cable Length Specification DescriptionDevice Profiles The Object ModelA.2.4 Configuration Procedure A.2.3 Network ConfigurationA.2 LM10 and GE Fanuc 90-30 with DeviceNet A.2.1 OverviewZ Select GE LM10 under GE Multilin A.2.5 Polling Input/Output ConnectionZ Also, set the Scan Interval and Reconnect Time Page Phase A values are displayed in %I00105 223 ⋅ 0.1 amps A.2.7 Cyclic Input/Output Connection A.2.6 COS Change of State Input/Output ConnectionMonitoring Data A.2.8 Explicit MessagingRung 3 has a Block Move word, 3 blocks FIGURE A-1 Ladder Logic for Data Monitoring Login Configuration Level to the LM10FIGURE A-2 Ladder Logic for Login Configuration Making Setting ChangesFIGURE A-3 Ladder Logic for Setting Changes Login User Level to the LM10FIGURE A-4 Ladder Logic for Login User A.3.4 Setting Up the DeviceNet Network A.3.2 System SetupA.3 LM10 and Allen-Bradley SLC500 via DeviceNet A.3.1 DescriptionA.3.5 Changing the Mode of Operation A.3.6 Configuring the Slave Device A.3.7 Control and Monitoring of the LM10 A.3.8 Explicit Messaging with the LM10 Relay A.3.9 Data Table Layout Table A-3 Status Codes Provided by ODVA SpecificationTable A-4 Data Table Layout Table A-5 Data to Get Trip Class A.3.10 Ladder LogicTable A-6 Data for Explicit Message Response, M1 Transferred to N20 Table A-8 Data for Explicit Message Response, M1 Transferred to N20 Table A-7 Data to Get Motor Run TimeInstance, and Attribute A-25 FIGURE A-9 Ladder Logic, Rungs 0000 toA-26 FIGURE A-10 Ladder Logic, Rungs 0006 toA-27 FIGURE A-11 Ladder Logic, Rungs 0009 toA-28 Index Page LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL INDEX