GE LM10 Special Application, F25 Input Switch Status 16-bit value use only lower byte

Page 67

CHAPTER 5: COMMUNICATIONS

 

DEVICENET OPERATIONS

 

 

 

 

 

Bitmask

Status

 

 

 

 

 

 

1--- ---- ---- ----

Motor hot at time of fault

 

 

 

 

 

The third 4-bit section is an enumeration which indicates the cause of the fault.

Value

Bitmask

Status

 

 

 

0

---- 0000 ---- ----

None

1

---- 0001 ---- ----

Overcurrent

 

 

 

2

---- 0010 ---- ----

Ground fault

 

 

 

3

---- 0011 ---- ----

Jam lock

 

 

 

4

---- 0100 ---- ----

Stall aux

 

 

 

5

---- 0101 ---- ----

Current unbalance

 

 

 

6

---- 0110---- ----

Aux sense

 

 

 

7

---- 0111 ---- ----

Load loss

 

 

 

8

---- 1000 ---- ----

Reserved

9

---- 1001 ---- ----

Reserved

10

---- 1010 ---- ----

DeviceNet

 

 

 

11

---- 1011 ---- ----

Operating voltage

 

 

 

F25: Input Switch Status (16-bit value; use only lower byte)

Format: two bytes in format 0xHHLL, where LL is the Switch Input status and HH is

Reserved.

Bitmask (LL)

Status

 

 

---- ---1

Stop switch input switch

 

 

---- --1-

Reset switch input switch

 

 

---- -1--

Run1 switch input switch

 

 

---- 1---

Run2 switch input switch

 

 

---1 ----

Auxsense1 switch input switch

 

 

--1- ----

Auxsense2 switch input switch

 

 

F26: Remaining Cool-Down Period - Format: two bytes in format 0xHHLL, where LL is the

Remaining Cool-Down Period and HH is Reserved. Byte LL Range: 0 to 99

5.1.12 Special Application

The LM10 Motor Protection System has a DeviceNet interface. The DEVICENET CONTROL input will set the RUN control to be operated using the DeviceNet interface. For this application we will assume this input to be tied active. This will disable any hard-wired

120 V AC RUN inputs from being accepted as a command to the LM10. The LM10 can read the state of these inputs through the DeviceNet protocol.

With the use of this read request the DeviceNet scanner (PLC or Master) can check the state of the local switches. After evaluating that all conditions of the system are appropriate the RUN command can be sent to the LM10 through the DeviceNet link. The RESET and STOP inputs do remain active at all times. The STOP input will command the LM10 to stop the motor even though the DeviceNet is the controlling input. The DeviceNet scanner would be able to detect this stop by monitoring the LM10 status. The status word can be polled or setup as a Cos/Cyclic.

Auxiliary sense inputs are also activated by a 120 V AC signal. If the end user desires, he may use these inputs for an alternate purpose if the Auxiliary Sense capability of the LM10 is disabled. The data is part of the same word as the RUN inputs.

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

5–61

Image 67
Contents 1601-0165-A6 LM10 Motor Protection System Instruction ManualGE Consumer & Industrial Multilin2008 GE Multilin Incorporated. All rights reserved 3 INTERFACE Table of Contents2 INSTALLATION 1 INTRODUCTIONAPPENDIX 4 FUNCTIONALITY5 COMMUNICATIONS 6 MISCELLANEOUSA-17 INDEX1-IV 1.1 Description LM10 Motor Protection System Chapter 1 Introduction1.1.1 The LM10 Relay 1.2.3 Relay Outputs 1.2.1 Features1.2 Overview 1.2.2 Current and Voltage Inputs1.2.5 Block Diagram 1.2.4 Power SupplyFIGURE 1-1 Functional Block Diagram 1.3.1 Programming and Display Unit 1.3 Features1.3.2 LED Indicators 1.3.3 SwitchesBaud Rate Changes to switch settings will not take effect until power is cycledDIP Switch Position FIGURE 1-2 LM10 FeaturesLM10 1.4 Ordering1.4.1 Order Codes Table 1-1 LM10 Order Codes1.5.1 Protection Elements SpecificationsGROUND FAULT PHASE CURRENT1.5.3 Control Functions POWERPOWER FACTOR POWER SUPPLY200 to CONTACT INPUTStop, Reset, DeviceNet control 0 to 1201.5.6 Outputs 1.5.5 CT DimensionsGround fault CT Thermal overload CT1.5.8 EnvironmentalApprovals/Certification SERIAL COMMUNICATIONS1-12 2.1.2 RS232 Port LM10 Motor Protection System Chapter 2 Installation2.1 Wiring 2.1.1 DeviceNetTable 2-1 Control Connections 2.1.3 Control Terminals2.1.4 Sensor Pack Input 2.1.5 Wiring DiagramCHAPTER 2 INSTALLATION FIGURE 2-4 LM10 Wiring Diagram2.2.1 LM10 Mounting 2.2 MountingFIGURE 2-6 LM10 Backplate Dimensions 2.2.2 PDU Door MountFIGURE 2-7 PDU Door-mount Dimensions 3.1.2 LEDs LM10 Motor Protection System Chapter 3 Interface3.1 PDU Operations 3.1.1 Liquid Crystal Displaypower factor, kW, average current, and current unbalance. Pressing the History button again advances to the next history record 3.2.2 History Record and Status Screens 3.2.3 Configuration Menu3.2 PDU Screens and Menus 3.2.1 Main Startup ScreenRun 2 to Run 1 delay between forward and reverse or between speeds 3.3.1 Description 3.3 EnerVista LM10 Software3.3.2 Functional Details Table 3-1 EnerVista Hot Keys LM10 Motor Protection System Chapter 4 Functionality 4.1 Overcurrent Fault Conditions4.1.1 Descriptions CHAPTER 4 FUNCTIONALITY FIGURE 4-1 Cold Motor Trip Curves FIGURE 4-2 Hot Motor Trip CurvesFIGURE 4-3 Trip Curve with Jam and Stall Enabled 4.1.2 Trip Curves ExampleFIGURE 4-4 Cool Down Times Page 4.2.1 Overview 4.2 Configuration SettingsTable 4-1 LM10 Programmable Parameters CONFIGURATION SETTINGSCHAPTER 4 FUNCTIONALITY 4.2.2 Main Menu4-30 4.2.4 CTs and CPTs PATH Configuration Ø ENGLISH/SPANISHPATH Configuration ØØ CTs & CPTs 4.2.3 Language4.2.5 Starter Type 4.2.6 Run 1 and Run 2 SetupPATH Configuration ØØØ Starter Type PATH Configuration ØØØØ Run 1 SetupΔ = phase current - average current 4.2.7 Time Delays 4.2.8 Other SettingsPATH Configuration ØØØØØ Time Delays PATH Configuration ØØØØØØ Other SettingsAuto Restart off DevNet Fault onReset Run Hrs Maintained offPATH Configuration ØØØØØØØ Aux Relay Faults 4.2.9 Auxiliary Relay FaultsPATH Configuration ØØØØØØØØ Aux Relay Faults 4.2.10 Passcode and Login4.2.11 Run Operations 4.2.12 Factory DefaultPATH Configuration ØØØØØØØØØ Run Operations PATH Configuration ØØØØØØØØØØ Factory DefaultRange 4.3 Status Values4.3.1 Main Menu Run, FaultThis value can be reset via the Reset Run Hrs configuration setting Fault, Dev Stop, Voltage, Aux Sense Range 0.0 to 3200.0 A 4.4 History Values4.4.1 Last Trip Data Range Overcurrent, Gr. Fault, Jam, Stall CuUnbalance, LdLoss, DevNetMotor Stop AUX Sense 1 Fault4.5 Motor Start/Stop Logic Motor Status RunningRUN1 PDU Command Motor RUN CommandsMotor STOP Commands RUN1 Switch Input4-44 5.1.2 Poll Data LM10 Motor Protection System Chapter 5 Communications5.1 DeviceNet Operations 5.1.1 DescriptionTable 5-4 Poll Data Group Table 5-1 Poll Data GroupTable 5-2 Poll Data Group Table 5-3 Poll Data GroupUINT = 16 bit unsigned integer 5.1.3 Identity object5.1.4 Message Router 5.1.5 DeviceNet ObjectBaud Rate, value 0 to 2 125, 250, and 500 kbps 5.1.6 Assembly ObjectDevice outputs see format and mapping below Assembly Object, Class Code 4, Instance see below Data Formats for Device InputsCHAPTER 5 COMMUNICATIONS Assembly Object, Class Code 4, Instance Connection Object, Class Code 5, Services 5.1.7 Connection ObjectConnection Object, Class Code 5, Attributes Connection Object, Class Code 5, Instance 2 polled input/output connection 5.1.9 Overload Object 5.1.8 ACK Handler ObjectUSINT = 8-bit unsigned integer UINT = 16-bit unsigned integer UINT = 16-bit unsigned integer 5.1.10 Extension ObjectData Type F1 Full Load Current 16-bit unsigned integer F2 Ground FaultF7 Power Transformer 5.1.11 Data FormatsF12 Starter Type F11 Auxiliary Relay Faults 16-bit bitmaskF9 Auxiliary Sense 1 / Run1-Run2 Time Delays F10 Auxiliary Sense 2 / Run2-Run1 Time DelaysF17 Trip Class F14 Other Settings 16-bit BitmaskF15 Poll Data Group enumeration 16-bit unsigned integer F16 Run1-Run2 and Run2-Run1 Time Delay 16-bit unsigned integerF24 Status Word 16-bit bitmask F21 Motor Status 8-bit BitmaskF22 Motor Status 16-bit bitmask F23 16-bit Unsigned Integer5.1.12 Special Application F25 Input Switch Status 16-bit value use only lower byteSent by scanner CANID, MACID, 0x0E, 0x64, 0x01 5.2.1 Description 5.2 Serial Port5-64 6.1.2 Changes to the Manual LM10 Motor Protection System Chapter 6 MiscellaneousRevision History 6.1.1 Release DatesChanges to Connection Object, Class Code 5, Instance 2 polled Table 6-4 Changes to Manual Since Release A3Change to Assembly Object, Class Code 4, Instance 101, Attribute Add Assembly Object, Class Code 4, Instance 105 Poll Data Group6.2.1 GE Multilin Warranty 6.2 Warranty6-68 WARRANTYCHAPTER 6 MISCELLANEOUS A.1 DeviceNet Overview LM10 Motor Protection System Appendix AA.1.1 Description A.1.3 DeviceNet Operations A.1.2 Controller Area Network CANA.1.7 Maximum Cable Lengths for DeviceNet A.1.6 DeviceNet FeaturesA.1.4 Explicit Messaging and Input/Output I/O Messaging A.1.5 Pre-defined Master/Slave Connection SetDescription A.1.8 DeviceNet Specification HighlightsTable A-1 Trunk Cable Length Specification Table A-2 Drop Cable Length SpecificationDevice Profiles The Object ModelA.2.1 Overview A.2.3 Network ConfigurationA.2.4 Configuration Procedure A.2 LM10 and GE Fanuc 90-30 with DeviceNetZ Select GE LM10 under GE Multilin A.2.5 Polling Input/Output ConnectionZ Also, set the Scan Interval and Reconnect Time Page Phase A values are displayed in %I00105 223 ⋅ 0.1 amps A.2.7 Cyclic Input/Output Connection A.2.6 COS Change of State Input/Output ConnectionMonitoring Data A.2.8 Explicit MessagingRung 3 has a Block Move word, 3 blocks FIGURE A-1 Ladder Logic for Data Monitoring Login Configuration Level to the LM10FIGURE A-2 Ladder Logic for Login Configuration Making Setting ChangesFIGURE A-3 Ladder Logic for Setting Changes Login User Level to the LM10FIGURE A-4 Ladder Logic for Login User A.3.1 Description A.3.2 System SetupA.3.4 Setting Up the DeviceNet Network A.3 LM10 and Allen-Bradley SLC500 via DeviceNetA.3.5 Changing the Mode of Operation A.3.6 Configuring the Slave Device A.3.7 Control and Monitoring of the LM10 A.3.8 Explicit Messaging with the LM10 Relay A.3.9 Data Table Layout Table A-3 Status Codes Provided by ODVA SpecificationTable A-4 Data Table Layout Table A-5 Data to Get Trip Class A.3.10 Ladder LogicTable A-6 Data for Explicit Message Response, M1 Transferred to N20 Table A-8 Data for Explicit Message Response, M1 Transferred to N20 Table A-7 Data to Get Motor Run TimeInstance, and Attribute A-25 FIGURE A-9 Ladder Logic, Rungs 0000 toA-26 FIGURE A-10 Ladder Logic, Rungs 0006 toA-27 FIGURE A-11 Ladder Logic, Rungs 0009 toA-28 Index Page LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL INDEX