GE LM10 A.1.4 Explicit Messaging and Input/Output I/O Messaging, A.1.6 DeviceNet Features

Page 77

CHAPTER A:

DEVICENET OVERVIEW

A.1.4 Explicit Messaging and Input/Output (I/O) Messaging

Explicit messages contain information such as vendors, parameters, etc. of a device. This information is comparatively less important than the I/O message; as such, it is sent with a higher CAN identifier as not to disturb the exchange of I/O messages on the bus.

Input/Output (I/O) messages contain the real-time I/O information of a device. In order to achieve “real time”, these messages are sent as quick as possible; therefore, they are sent with a lower CAN identifier than explicit messages.

A.1.5 Pre-defined Master/Slave Connection Set

A set of connection identifiers known as the Pre-defined Master/Slave Connection Set has been specified to simplify the movement of I/O configuration-type data typically seen in a master/slave architecture. An important benefit is that the establishment of connections from the pre-defined set is simplified considerably. Only a few messages are required to have I/O connections up and running. The pre-defined set contains one explicit messaging connection and allows several different I/O connections including:

bit strobed command/response

polled command/response

change of state

cyclic

A.1.6 DeviceNet Features

DeviceNet's features include:

1.Low cost.

2.High speed. DeviceNet supports 3 baud rates: 125 kbps, 250 kbps, and 500 kbps. This meets 95% of typical industrial requirements.

3.Reliability. DeviceNet uses the well proven CAN protocol with application layers that have undergone strict conformance testing to ensure reliability.

4.Support of up to 64 active nodes.

5.Easy installation.

6.Removal and replacement of devices from the network under power.

7.0 to 8 byte data packets.

8.Linear (trunk line/drop line) bus topology, with power and signal on the same network cable.

A.1.7 Maximum Cable Lengths for DeviceNet

DeviceNet defines the maximum cable lengths (trunk and drop cables) to ensure the propagation of the transmitted message falls within the acceptable limits. The upper boundaries of the trunk cable and drop cable length are shown below.

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

A–3

Image 77
Contents GE Consumer & Industrial LM10 Motor Protection System Instruction ManualMultilin 1601-0165-A62008 GE Multilin Incorporated. All rights reserved 2 INSTALLATION Table of Contents1 INTRODUCTION 3 INTERFACE5 COMMUNICATIONS 4 FUNCTIONALITY6 MISCELLANEOUS APPENDIXA-17 INDEX1-IV 1.1.1 The LM10 Relay LM10 Motor Protection System Chapter 1 Introduction1.1 Description 1.2 Overview 1.2.1 Features1.2.2 Current and Voltage Inputs 1.2.3 Relay OutputsFIGURE 1-1 Functional Block Diagram 1.2.4 Power Supply1.2.5 Block Diagram 1.3.2 LED Indicators 1.3 Features1.3.3 Switches 1.3.1 Programming and Display UnitDIP Switch Position Changes to switch settings will not take effect until power is cycledFIGURE 1-2 LM10 Features Baud Rate1.4.1 Order Codes 1.4 OrderingTable 1-1 LM10 Order Codes LM10GROUND FAULT SpecificationsPHASE CURRENT 1.5.1 Protection ElementsPOWER FACTOR POWERPOWER SUPPLY 1.5.3 Control FunctionsStop, Reset, DeviceNet control CONTACT INPUT0 to 120 200 toGround fault CT 1.5.5 CT DimensionsThermal overload CT 1.5.6 OutputsApprovals/Certification EnvironmentalSERIAL COMMUNICATIONS 1.5.81-12 2.1 Wiring LM10 Motor Protection System Chapter 2 Installation2.1.1 DeviceNet 2.1.2 RS232 PortTable 2-1 Control Connections 2.1.3 Control Terminals2.1.4 Sensor Pack Input 2.1.5 Wiring DiagramCHAPTER 2 INSTALLATION FIGURE 2-4 LM10 Wiring Diagram2.2.1 LM10 Mounting 2.2 MountingFIGURE 2-7 PDU Door-mount Dimensions 2.2.2 PDU Door MountFIGURE 2-6 LM10 Backplate Dimensions 3.1 PDU Operations LM10 Motor Protection System Chapter 3 Interface3.1.1 Liquid Crystal Display 3.1.2 LEDspower factor, kW, average current, and current unbalance. Pressing the History button again advances to the next history record 3.2 PDU Screens and Menus 3.2.3 Configuration Menu3.2.1 Main Startup Screen 3.2.2 History Record and Status ScreensRun 2 to Run 1 delay between forward and reverse or between speeds 3.3.2 Functional Details 3.3 EnerVista LM10 Software3.3.1 Description Table 3-1 EnerVista Hot Keys 4.1.1 Descriptions 4.1 Overcurrent Fault ConditionsLM10 Motor Protection System Chapter 4 Functionality CHAPTER 4 FUNCTIONALITY FIGURE 4-1 Cold Motor Trip Curves FIGURE 4-2 Hot Motor Trip CurvesFIGURE 4-4 Cool Down Times 4.1.2 Trip Curves ExampleFIGURE 4-3 Trip Curve with Jam and Stall Enabled Page Table 4-1 LM10 Programmable Parameters 4.2 Configuration Settings4.2.1 Overview 4-30 4.2.2 Main MenuCONFIGURATION SETTINGSCHAPTER 4 FUNCTIONALITY PATH Configuration ØØ CTs & CPTs PATH Configuration Ø ENGLISH/SPANISH4.2.3 Language 4.2.4 CTs and CPTsPATH Configuration ØØØ Starter Type 4.2.6 Run 1 and Run 2 SetupPATH Configuration ØØØØ Run 1 Setup 4.2.5 Starter TypeΔ = phase current - average current PATH Configuration ØØØØØ Time Delays 4.2.8 Other SettingsPATH Configuration ØØØØØØ Other Settings 4.2.7 Time DelaysReset Run Hrs DevNet Fault onMaintained off Auto Restart offPATH Configuration ØØØØØØØ Aux Relay Faults 4.2.9 Auxiliary Relay FaultsPATH Configuration ØØØØØØØØ Aux Relay Faults 4.2.10 Passcode and LoginPATH Configuration ØØØØØØØØØ Run Operations 4.2.12 Factory DefaultPATH Configuration ØØØØØØØØØØ Factory Default 4.2.11 Run Operations4.3.1 Main Menu 4.3 Status ValuesRun, Fault RangeThis value can be reset via the Reset Run Hrs configuration setting 4.4.1 Last Trip Data 4.4 History ValuesRange Overcurrent, Gr. Fault, Jam, Stall CuUnbalance, LdLoss, DevNet Fault, Dev Stop, Voltage, Aux Sense Range 0.0 to 3200.0 A4.5 Motor Start/Stop Logic AUX Sense 1 FaultMotor Status Running Motor StopMotor STOP Commands Motor RUN CommandsRUN1 Switch Input RUN1 PDU Command4-44 5.1 DeviceNet Operations LM10 Motor Protection System Chapter 5 Communications5.1.1 Description 5.1.2 Poll DataTable 5-2 Poll Data Group Table 5-1 Poll Data GroupTable 5-3 Poll Data Group Table 5-4 Poll Data Group5.1.4 Message Router 5.1.3 Identity object5.1.5 DeviceNet Object UINT = 16 bit unsigned integerDevice outputs see format and mapping below 5.1.6 Assembly ObjectBaud Rate, value 0 to 2 125, 250, and 500 kbps Assembly Object, Class Code 4, Instance CHAPTER 5 COMMUNICATIONS Data Formats for Device Inputssee below Assembly Object, Class Code 4, Instance Connection Object, Class Code 5, Attributes 5.1.7 Connection ObjectConnection Object, Class Code 5, Services Connection Object, Class Code 5, Instance 2 polled input/output connection USINT = 8-bit unsigned integer UINT = 16-bit unsigned integer 5.1.8 ACK Handler Object5.1.9 Overload Object UINT = 16-bit unsigned integer 5.1.10 Extension ObjectAttribute F7 Power Transformer F2 Ground Fault5.1.11 Data Formats F1 Full Load Current 16-bit unsigned integerF9 Auxiliary Sense 1 / Run1-Run2 Time Delays F11 Auxiliary Relay Faults 16-bit bitmaskF10 Auxiliary Sense 2 / Run2-Run1 Time Delays F12 Starter TypeF15 Poll Data Group enumeration 16-bit unsigned integer F14 Other Settings 16-bit BitmaskF16 Run1-Run2 and Run2-Run1 Time Delay 16-bit unsigned integer F17 Trip ClassF22 Motor Status 16-bit bitmask F21 Motor Status 8-bit BitmaskF23 16-bit Unsigned Integer F24 Status Word 16-bit bitmask5.1.12 Special Application F25 Input Switch Status 16-bit value use only lower byteSent by scanner CANID, MACID, 0x0E, 0x64, 0x01 5.2.1 Description 5.2 Serial Port5-64 Revision History LM10 Motor Protection System Chapter 6 Miscellaneous6.1.1 Release Dates 6.1.2 Changes to the ManualChange to Assembly Object, Class Code 4, Instance 101, Attribute Table 6-4 Changes to Manual Since Release A3Add Assembly Object, Class Code 4, Instance 105 Poll Data Group Changes to Connection Object, Class Code 5, Instance 2 polled6.2.1 GE Multilin Warranty 6.2 WarrantyCHAPTER 6 MISCELLANEOUS WARRANTY6-68 A.1.1 Description LM10 Motor Protection System Appendix AA.1 DeviceNet Overview A.1.3 DeviceNet Operations A.1.2 Controller Area Network CANA.1.4 Explicit Messaging and Input/Output I/O Messaging A.1.6 DeviceNet FeaturesA.1.5 Pre-defined Master/Slave Connection Set A.1.7 Maximum Cable Lengths for DeviceNetTable A-1 Trunk Cable Length Specification A.1.8 DeviceNet Specification HighlightsTable A-2 Drop Cable Length Specification DescriptionDevice Profiles The Object ModelA.2.4 Configuration Procedure A.2.3 Network ConfigurationA.2 LM10 and GE Fanuc 90-30 with DeviceNet A.2.1 OverviewZ Also, set the Scan Interval and Reconnect Time A.2.5 Polling Input/Output ConnectionZ Select GE LM10 under GE Multilin Page Phase A values are displayed in %I00105 223 ⋅ 0.1 amps A.2.7 Cyclic Input/Output Connection A.2.6 COS Change of State Input/Output ConnectionMonitoring Data A.2.8 Explicit MessagingRung 3 has a Block Move word, 3 blocks FIGURE A-1 Ladder Logic for Data Monitoring Login Configuration Level to the LM10FIGURE A-2 Ladder Logic for Login Configuration Making Setting ChangesFIGURE A-3 Ladder Logic for Setting Changes Login User Level to the LM10FIGURE A-4 Ladder Logic for Login User A.3.4 Setting Up the DeviceNet Network A.3.2 System SetupA.3 LM10 and Allen-Bradley SLC500 via DeviceNet A.3.1 DescriptionA.3.5 Changing the Mode of Operation A.3.6 Configuring the Slave Device A.3.7 Control and Monitoring of the LM10 A.3.8 Explicit Messaging with the LM10 Relay Table A-4 Data Table Layout Table A-3 Status Codes Provided by ODVA SpecificationA.3.9 Data Table Layout Table A-6 Data for Explicit Message Response, M1 Transferred to N20 A.3.10 Ladder LogicTable A-5 Data to Get Trip Class Instance, and Attribute Table A-7 Data to Get Motor Run TimeTable A-8 Data for Explicit Message Response, M1 Transferred to N20 A-25 FIGURE A-9 Ladder Logic, Rungs 0000 toA-26 FIGURE A-10 Ladder Logic, Rungs 0006 toA-27 FIGURE A-11 Ladder Logic, Rungs 0009 toA-28 Index Page LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL INDEX