GE Motor Protection System, LM10 instruction manual Sent by scanner CANID, MACID, 0x0E, 0x64, 0x01

Page 68
•Sent by scanner: CANID, MACID, 0x0E, 0x64, 0x01, 0x34

DEVICENET OPERATIONS

CHAPTER 5: COMMUNICATIONS

This data was initially setup for development purposes. An explicit message through the custom class 100(0x64) is the only way to access this data. The DeviceNet message to read this data is: service 0x0e, class 0x64, instance 1, and attribute 0x34. The response will be a 16-bit word with MACID switches in the high byte and AC switch input bits in the low byte.

Sent by scanner: CANID, MACID, 0x0E, 0x64, 0x01, 0x34

Response from the LM10: CANID, MACID, 0x8E, LBY, HBY

The format of this data follows F25: Input Switch Status. The high byte (HBY) is not used in this application. The low byte (LBY) is the input data we are looking for. The seven hard wired inputs map to bits 0 to 6 as DeviceNet Control, AxSn2, AxSn1, RUN2, RUN1, Reset, Stop. To watch for RUN1 one would test for bit 2 being on. EX: LBY and 0x04 is not equal to 0x00.

Do not switch out of DeviceNet Control while the motor is running. In such a case the LM10 will issue a Stop command under the assumption that the network is down.

5–62

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL

Image 68
Contents LM10 Motor Protection System Instruction Manual GE Consumer & IndustrialMultilin 1601-0165-A62008 GE Multilin Incorporated. All rights reserved Table of Contents 2 INSTALLATION1 INTRODUCTION 3 INTERFACE4 FUNCTIONALITY 5 COMMUNICATIONS6 MISCELLANEOUS APPENDIXINDEX A-171-IV 1.1.1 The LM10 Relay LM10 Motor Protection System Chapter 1 Introduction1.1 Description 1.2.1 Features 1.2 Overview1.2.2 Current and Voltage Inputs 1.2.3 Relay OutputsFIGURE 1-1 Functional Block Diagram 1.2.4 Power Supply1.2.5 Block Diagram 1.3 Features 1.3.2 LED Indicators1.3.3 Switches 1.3.1 Programming and Display UnitChanges to switch settings will not take effect until power is cycled DIP Switch PositionFIGURE 1-2 LM10 Features Baud Rate1.4 Ordering 1.4.1 Order CodesTable 1-1 LM10 Order Codes LM10Specifications GROUND FAULTPHASE CURRENT 1.5.1 Protection ElementsPOWER POWER FACTORPOWER SUPPLY 1.5.3 Control FunctionsCONTACT INPUT Stop, Reset, DeviceNet control0 to 120 200 to1.5.5 CT Dimensions Ground fault CTThermal overload CT 1.5.6 OutputsEnvironmental Approvals/CertificationSERIAL COMMUNICATIONS 1.5.81-12 LM10 Motor Protection System Chapter 2 Installation 2.1 Wiring2.1.1 DeviceNet 2.1.2 RS232 Port2.1.3 Control Terminals Table 2-1 Control Connections2.1.5 Wiring Diagram 2.1.4 Sensor Pack InputFIGURE 2-4 LM10 Wiring Diagram CHAPTER 2 INSTALLATION2.2 Mounting 2.2.1 LM10 MountingFIGURE 2-7 PDU Door-mount Dimensions 2.2.2 PDU Door MountFIGURE 2-6 LM10 Backplate Dimensions LM10 Motor Protection System Chapter 3 Interface 3.1 PDU Operations3.1.1 Liquid Crystal Display 3.1.2 LEDspower factor, kW, average current, and current unbalance. Pressing the History button again advances to the next history record 3.2.3 Configuration Menu 3.2 PDU Screens and Menus3.2.1 Main Startup Screen 3.2.2 History Record and Status ScreensRun 2 to Run 1 delay between forward and reverse or between speeds 3.3.2 Functional Details 3.3 EnerVista LM10 Software3.3.1 Description Table 3-1 EnerVista Hot Keys 4.1.1 Descriptions 4.1 Overcurrent Fault ConditionsLM10 Motor Protection System Chapter 4 Functionality FIGURE 4-1 Cold Motor Trip Curves FIGURE 4-2 Hot Motor Trip Curves CHAPTER 4 FUNCTIONALITYFIGURE 4-4 Cool Down Times 4.1.2 Trip Curves ExampleFIGURE 4-3 Trip Curve with Jam and Stall Enabled Page Table 4-1 LM10 Programmable Parameters 4.2 Configuration Settings4.2.1 Overview 4-30 4.2.2 Main MenuCONFIGURATION SETTINGSCHAPTER 4 FUNCTIONALITY PATH Configuration Ø ENGLISH/SPANISH PATH Configuration ØØ CTs & CPTs4.2.3 Language 4.2.4 CTs and CPTs4.2.6 Run 1 and Run 2 Setup PATH Configuration ØØØ Starter TypePATH Configuration ØØØØ Run 1 Setup 4.2.5 Starter TypeΔ = phase current - average current 4.2.8 Other Settings PATH Configuration ØØØØØ Time DelaysPATH Configuration ØØØØØØ Other Settings 4.2.7 Time DelaysDevNet Fault on Reset Run HrsMaintained off Auto Restart off4.2.9 Auxiliary Relay Faults PATH Configuration ØØØØØØØ Aux Relay Faults4.2.10 Passcode and Login PATH Configuration ØØØØØØØØ Aux Relay Faults4.2.12 Factory Default PATH Configuration ØØØØØØØØØ Run OperationsPATH Configuration ØØØØØØØØØØ Factory Default 4.2.11 Run Operations4.3 Status Values 4.3.1 Main MenuRun, Fault RangeThis value can be reset via the Reset Run Hrs configuration setting 4.4 History Values 4.4.1 Last Trip DataRange Overcurrent, Gr. Fault, Jam, Stall CuUnbalance, LdLoss, DevNet Fault, Dev Stop, Voltage, Aux Sense Range 0.0 to 3200.0 AAUX Sense 1 Fault 4.5 Motor Start/Stop LogicMotor Status Running Motor StopMotor RUN Commands Motor STOP CommandsRUN1 Switch Input RUN1 PDU Command4-44 LM10 Motor Protection System Chapter 5 Communications 5.1 DeviceNet Operations5.1.1 Description 5.1.2 Poll DataTable 5-1 Poll Data Group Table 5-2 Poll Data GroupTable 5-3 Poll Data Group Table 5-4 Poll Data Group5.1.3 Identity object 5.1.4 Message Router5.1.5 DeviceNet Object UINT = 16 bit unsigned integerDevice outputs see format and mapping below 5.1.6 Assembly ObjectBaud Rate, value 0 to 2 125, 250, and 500 kbps Assembly Object, Class Code 4, Instance CHAPTER 5 COMMUNICATIONS Data Formats for Device Inputssee below Assembly Object, Class Code 4, Instance Connection Object, Class Code 5, Attributes 5.1.7 Connection ObjectConnection Object, Class Code 5, Services Connection Object, Class Code 5, Instance 2 polled input/output connection USINT = 8-bit unsigned integer UINT = 16-bit unsigned integer 5.1.8 ACK Handler Object5.1.9 Overload Object 5.1.10 Extension Object UINT = 16-bit unsigned integerAccess F2 Ground Fault F7 Power Transformer5.1.11 Data Formats F1 Full Load Current 16-bit unsigned integerF11 Auxiliary Relay Faults 16-bit bitmask F9 Auxiliary Sense 1 / Run1-Run2 Time DelaysF10 Auxiliary Sense 2 / Run2-Run1 Time Delays F12 Starter TypeF14 Other Settings 16-bit Bitmask F15 Poll Data Group enumeration 16-bit unsigned integerF16 Run1-Run2 and Run2-Run1 Time Delay 16-bit unsigned integer F17 Trip ClassF21 Motor Status 8-bit Bitmask F22 Motor Status 16-bit bitmaskF23 16-bit Unsigned Integer F24 Status Word 16-bit bitmaskF25 Input Switch Status 16-bit value use only lower byte 5.1.12 Special ApplicationSent by scanner CANID, MACID, 0x0E, 0x64, 0x01 5.2 Serial Port 5.2.1 Description5-64 LM10 Motor Protection System Chapter 6 Miscellaneous Revision History6.1.1 Release Dates 6.1.2 Changes to the ManualTable 6-4 Changes to Manual Since Release A3 Change to Assembly Object, Class Code 4, Instance 101, AttributeAdd Assembly Object, Class Code 4, Instance 105 Poll Data Group Changes to Connection Object, Class Code 5, Instance 2 polled6.2 Warranty 6.2.1 GE Multilin WarrantyCHAPTER 6 MISCELLANEOUS WARRANTY6-68 A.1.1 Description LM10 Motor Protection System Appendix AA.1 DeviceNet Overview A.1.2 Controller Area Network CAN A.1.3 DeviceNet OperationsA.1.6 DeviceNet Features A.1.4 Explicit Messaging and Input/Output I/O MessagingA.1.5 Pre-defined Master/Slave Connection Set A.1.7 Maximum Cable Lengths for DeviceNetA.1.8 DeviceNet Specification Highlights Table A-1 Trunk Cable Length SpecificationTable A-2 Drop Cable Length Specification DescriptionThe Object Model Device ProfilesA.2.3 Network Configuration A.2.4 Configuration ProcedureA.2 LM10 and GE Fanuc 90-30 with DeviceNet A.2.1 OverviewZ Also, set the Scan Interval and Reconnect Time A.2.5 Polling Input/Output ConnectionZ Select GE LM10 under GE Multilin Page Phase A values are displayed in %I00105 223 ⋅ 0.1 amps A.2.6 COS Change of State Input/Output Connection A.2.7 Cyclic Input/Output ConnectionA.2.8 Explicit Messaging Monitoring DataRung 3 has a Block Move word, 3 blocks Login Configuration Level to the LM10 FIGURE A-1 Ladder Logic for Data MonitoringMaking Setting Changes FIGURE A-2 Ladder Logic for Login ConfigurationLogin User Level to the LM10 FIGURE A-3 Ladder Logic for Setting ChangesFIGURE A-4 Ladder Logic for Login User A.3.2 System Setup A.3.4 Setting Up the DeviceNet NetworkA.3 LM10 and Allen-Bradley SLC500 via DeviceNet A.3.1 DescriptionA.3.5 Changing the Mode of Operation A.3.6 Configuring the Slave Device A.3.7 Control and Monitoring of the LM10 A.3.8 Explicit Messaging with the LM10 Relay Table A-4 Data Table Layout Table A-3 Status Codes Provided by ODVA SpecificationA.3.9 Data Table Layout Table A-6 Data for Explicit Message Response, M1 Transferred to N20 A.3.10 Ladder LogicTable A-5 Data to Get Trip Class Instance, and Attribute Table A-7 Data to Get Motor Run TimeTable A-8 Data for Explicit Message Response, M1 Transferred to N20 FIGURE A-9 Ladder Logic, Rungs 0000 to A-25FIGURE A-10 Ladder Logic, Rungs 0006 to A-26FIGURE A-11 Ladder Logic, Rungs 0009 to A-27A-28 Index Page LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL INDEX LM10 MOTOR PROTECTION SYSTEM - INSTRUCTION MANUAL