Nordyne M3RL Series installation instructions Horizontal Venting

Page 18

Horizontal Venting

Vent and combustion air intake terminations must be as shown in Figure 19 unless the concentric vent termination kit is used.

!WARNING:

Ensure that the combustion air vent and the exhaust vent are configured as shown in Fig. 19. Improper vent termination can cause recirculation of the flue gases. This may result in furnace vibration. In severe cases, the furnace will cycle, due to the intermittent contact between the flame and the flame sensor. If you note these oscillations occurring, check the vent configuration. Make sure that the exhaust vent does not have a 90 degree termination.

For horizontal venting, either the Horizontal Exterior Vent Mounting Kit or the Concentric Vent Termination Kit may be used (See Table 12).

For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes.

The Horizontal Exterior Vent Mounting Kit con- sists of two face plates and an insulating gas- ket to seal the exterior surface. A hole sized closely to the pipe diameter must first be cut through the wall. A short length of pipe is then cut such that it can penetrate the wall and be held in place by closely fitting standard cou- plings. The face plates are retained on both sides of the wall by the couplings, and the gasket is retained against the wall by the outer face plate. Face plates must be fastened to the wall and the outside one must be flashed as appropriate to prevent entry of water.

When the above kits are not used the following steps are required:

1.Check the hole size cut through the exte- rior wall. Insure that the hole diameter is less than the diameter of the couplings to be used.

2.Extend the vent pipe through the wall approximately 1" and seal the area be- tween the wall and pipe.

3.Apply couplings to the vent pipe on the interior and exterior sides of the wall to insure the pipe can not be pushed or pulled through the wall.

4.Insure the combustion air inlet pipe has a 90 degree termination elbow, and is pointing downward as shown in Figures 19 & 20.

Note that a combustion air intake must be provided with an elbow opening downward.

When the vent pipe must exit an exterior wall close to the grade or expected snow level, a riser should be provided as shown in Figure 18. Insulation is required to prevent freezing of this section of pipe.

Vertical Venting

For vertical venting, either the configuration shown in Figure 20 or the Concentric Vent Termination Kit may be used. Vertical venting is one of the shortest routing methods when piping vents for furnaces. The M3 furnace operates trouble-free when the furnace is in- stalled with a shorter vent.

The inlet for the combustion intake pipe must be extended at least one foot above the roofline or snow accumulation level.

The outlet of the vent must be extended at least 10 inches above the inlet of the combustion air intake pipe.

The vent as well as the combustion air intake

pipe should be located on the same side of the roof. Both pipes must not be closer than 5 inches apart. They should not be separated more than 36 inches.

The roof penetration must be properly flashed and waterproofed with a plumbing roof boot or equivalent flashing. Termination spacing re- quirements from the roof and from each other must be per Figure 20.

Concentric Vent Termination

A concentric vent termination is approved for use with these furnaces (See Table 12). For proper installation of the concentric vent termi- nation, follow the installation instructions pro- vided with the kit.

18

Image 18
Contents Installation Instructions Page Table of Contents L 060 a a WGeneral Shipping WeightFurnace Specifications/Airflow Data Top ViewOwner Information General DescriptionInstallation Standards Manufacturer WARRANTY, OWNER’S ResponsibilitiesLocation Circulating AIR SupplyMinimum Clearances Duct Connectors Return AIR ProvisionsCloset or Alcove Ducted Return AIRDuct Connector Selection Duct InstallationAIR Distribution Systems CUT Duct Opening Finger Tabbed only Installing Platinum Series 14 Round Duct ConnectorInstalling Screw Down Duct CON- Nector Screw Down Platinum SeriesInstalling Finger Tabbed Duct CON- Nectors Alternate Attachment MethodsInstall Furnace Venting and Combustion AIR RequirementsGeneral Venting Requirements Furnace Must not be Common Vented with Other Appliances Vent Table Vent Termination Clearances for Direct Vent FurnacesVent Pipe Installation Vent Pipe MaterialDownflow Furnace Horizontal VentingHorizontal Venting Alternate Horizontal Vent Installation Drainage of Condensate from FurnaceFurnace with Condensate Drain Trap Assembly GAS Supply and PipingHigh Altitude Derate ConversionLeak Check To Turn Off Fuel Supply to the ApplianceTo Convert the Unit to the Alternate Gas To Remove the Burner AssemblyTo Remove the Burner Orifices Approximate Orifice Size for Natural and LP GasesLighting and Adjustment of the Appliance Convertible Pressure Regulator CapType of Fuel Manifold Pressure Electrical WiringLine Voltage Wiring Completing the ConversionLow Voltage Wiring Electrical DataSTART-UP and Adjustments Start-Up ProcedureVentilation Shut Down Procedure Sequence of OperationVerifying Firing Rate Gas Flow Rate Verifying Operation of the Supply Air Limit SwitchDescription of Components Verifying Burner OperationCombustion Air and Vent System MaintenanceAccessory Kits Air FilterLubrication Condensate Drain AssemblySystem Operation Information Blower CompartmentCooling Mode Furnace Fails to OperateM3 Downflow Furnace Downflow Furnace Wiring Diagram Page INSTALLATION/PERFORMANCE Check List Fuel Type¢7082197¤